yogokowa field bus system transmitter all's we are geting
IOP fault in Contiunes please help me fine how we can
normal the broblems?
Answer Posted / jigaranadkat
1) Infield bus system, IOP detection is different from HART system.
2) IOP will occur only for input e.g. transmitters.
3) One probability is there (which is most common) that your transmitter is under-ranged or PV value fluctuates highly (on wither ends). Being s digital system you will not receive IOP(-) in FF system.
4) Check for alarms and run integrity test (via PRM) and check if any of the internal blocks like AI or Transducer block or Resource Block is going to OOS (Out of service or Manual Mode).
5) Additional Check :
Check if you are receiving CNF error. If it comes then you may reset the transmitter by removing the power or isolating it from Loop.
This shall resolve the error. If not then you need to replace the transmitter.
Hope this helps.
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
how many type of plug are used in pneumatic control valve,name them.
What is hp & mp seperator .& what is its working principle ?
How earthing can be checked????
In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?
what is isloted barrier how it works and what are the main purpose.how it make safe area.
what is function of SCADA , and how is it work, explain with difination
Hi, Is there any smart plant instrumentation design training institute in Bangalore?
Explain the use of hair spring in the pressure gauge.
Why plc require in analog input 4-20amp & 0-10 volt?
what is the calibration procedure for transweigh make weigh feeder?
Give 2 application of quartz crystal used for process parameter measurement.
Questions on flow meters,few questions on HART protocol,
What is shielding effect?
Hi Friends i am going to write BARC written test by this month 20th (20-5-2008). So please if any body knows the details about this or having previous question papers pls mail me to kkumarei@gmail.com. For Suggestions give one message to 9962122264
OBJECTIVE TYPE QUESTIONS OF ANALYTICAL INSTRUMENTATION