Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

During the main stator winding insulation testing (phase to ground)of 11kv alternator (Lerysomer) i found 0 and resistance with multimeter and found 20 killo ohm while the power cables are connected both end (Generator & VCB). In VCB PT (Potential transformer) are connected.
Please any body explain that method of insulation is correct or not? also describe of PT connections

Answer Posted / k.prakashchandra

Supposing that you have disconnected the neutral of GEN , you will measure the dc resistance of PT as the other end of it is earthed . 20 K ohm will be measured as 0 M ohm by the megger . If you want to test insulation of GEN , you have to isolate the winding from everything .

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what about GD square and its important for motor design?

3888


what is the excess air in furnace

2099


Why Water motor is not taking a load or pressure while everything is correct. (Note: Motor running properly)

1457


What is meant by analogous system?

1368


If oil and air can withstand a high MeV when used as an insulator in a transformer, what are the values of how high for each material?

1967


how load of a turbo generator can be increased

2014


How To increase Knowledge Of boliler regarding To Only Electrical Field..

1668


what are the basic insulation levels & what its Unit

2066


What is time invariant system?

1224


control & auxilary circuits used for circuir breakers

1939


If only R Phase is connected in 2 pole elcb, n is not connected than it will work or not in ground fault.

1490


How to know any size of cable if there are not written on cable? Answer must be theurical not by experience.

2174


what percent do you derate your copper wire when you change from copper buss to copper wire

2042


I am shobana from Chennai. I am having my personal interview on 19th Dec at Chennai.kindly mail me the questions to mail id shobana.shanthi@gmail.com

2421


How to calculate Temp from Resister from PT100 equation,

1800