Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

3 phase supply is there Total kw 100 howmuch cable put the load

Answer Posted / khaled shaban

you have to calculate your ampere by using below equ.
I=P/Sqrt(3)*V*P.F
after that you have to select circuit breaker; after selection of CB check cable size referring to cable ratings as per manufacturer.
e.g. Volt 380V, with 100Kw and consider P.F=0.8
current will be 190A
cable should handle more than 190A, but first you have to choose MCCB for this load; the standard for your selection should be as following:
MCCB size = I*1.25 (1.25 at least)
so MCCB will be more than 237.5A (for standard MCCB you will select 250A)
hence your MCCB is 250A, your cable should be more than 250A.
As per cable manufacturer rating in my country, cable size should be (3*120+70)mm2 laid in duct, but in case if this cable laid in ground; cable size will be (3*90+50)mm2.

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?

2151


If a rotary UPS is in line through grid power; What would be the impact on Power Factor if the load through rotary ups is 25% , 50% , 75% & 100%. Will the power factor reduce with less load?

1883


what is settable hystersis protection? If any body knows plz kindly post the answer..

2058


What is the use of lag compensator?

1238


Why High voltage are generate noise ?

1520


some basic standard questions on transformer.

1800


where was current transformer protection units used and why??

2039


Can a generator runs after getting 1st stator earth fault.

1409


how generator load test is conducted?what are the steps?

1598


Why hydropower is called renewable source of energy?

1051


I NEED RRB APTITUDE QUESTIONS AND MODEL PAPER,PLEASE SEND MY E-MAIL joo28_eee@yahoo.co.in

1926


What will happened if the neutral of the (star connected secondry) Xformer disconnected? (if its Above KVA rated one)

2163


hi i have applied for lic of india south cenrtal zonal ,hyd. i didnt get hall ticket till now.let me know how can i get form internet

2002


Refernce currents are to be generated using refernce cueernts how can this be done??

2004


differnce between single acting and double acting solenoid valves

1845