Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how can we find a burden of potential transformer? what
does it effects? how can we calculate rated load of it?

Answer Posted / tuktuk

Dear Mr.Raghavendran,
Thank you for your answer, I have the same problem but after reading your answer I still have some concerns.
I am really confused. In this case, we do not know the rated burden of the VT. Now we have to calculate the total burden and then selecte the rated value from IEC standards.

__Ztotal, which you mentioned above, is in Ohm or VA?
__Zsec and Zrelay we can get the value from manufacturer but Zlead, is it calculated by this formula: Zlead= (p*L)/S
(where: p is specific resistivity of copper in ohm.mm^2/m; L is length of lead between the PT secondary and the relay in meter; S is the section of lead in sqmm)? Is this true?
__I dont know how can we get secondary current Isec? (I guess Isec=Usec/Zt, isn't it?)
__And Burden in VA = Zt*Isec. As Ohm law, we have P=VI=RI^2=U^2/R, I do not understand the formula that you used to calculate Burden of VT in VA
Hope that you could help me to solve this stuck in my head.

Thank you.

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

PIU how does work?

2435


Explain about Leakage Test.

2001


If there is major % of Voltage harmonics in the system, how can it be control or reduced?

1989


state basic meaning of 'INDUSTIAL AUTOMATION'?

1943


how can we say that stator magnetic field rotates with synchronous speed?can we derive?

1770


What is the formula to calculate the no load current of a single & three phase induction motor

2276


For refrigerators the motor current is raised beyond its rating on both conditions when the voltage of the system is more(say 270v) than the rated voltage(220v) as well as when the voltage of system is less(say 160v) than normal voltageof 220v, why explain?

1973


what is the prosses for getting of 33kv licence (i have completed my engineering degree & working in 33kv substation for contract basis )????

1942


How do you calculate the actual power consumption of an inductive load appliance. Say, a deep freezer of 200watts

2133


Explain Active power,reactive power,how its related to each other , & inductive ,capacitive.

1936


what is the standard values(Megger test) of resistances between L&N,L&E and N&E for a system on IEE regulations?

2264


How you calculating the 30 Hp 3 phase AC motor of power what size of cable is used for this motor?

1662


What is the difference between hot and cold loop testing?

1144


how we decide scurt (disc) of insulator with respect to kv rating

3569


what is earth fault relay 64T, why it is used in main Incomer and neutral CT of Transformer.

3795