Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how many ht 11 kv cable size for 11kv 2000 kva 11kv*433v transformer ?

Answer Posted / prashant soni

HT Cable size dependson fault level to be withstood and its duration..

If you take XLPE, HT Cable of ALU conductor,
condiering 350MVA for 1 sec *(18.37kA), min. C/A will be found out by Area(A) = (Short ckt current (kA)*Square root of Time)/k
k is constant = 0.094 for XLPE ALu conductor.

This will give you min. size required for HT system (11/22/33/6.6/3.3kV)

Choose nearest standard higher size for HT Cable..
primary 3*240 sqmm AL cable

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what will happen if there is a voltage leakage or current leakage in an electrical train

1949


why constant voltage transformer should be start without load? and if started then what will happen?

1992


i need project topics along with circuit diagram in the electrical and electronics engg and also some websites regarding projets.

2034


how to find 5 kilo meter long under ground 33 kv cable fault location if IR VALUE shows 0.05 M ohm @5000 volt.and cable fault locator shows some time fault distance 3 kilo meter ,3.7 kilo meter and some time 1 kilo meter? now how to find the fault location that where is leakage. note--it is tested with 5000 kv megger and insulation resistance is 0.05 M ohm. and some time 0.03 M ohm comes.

2156


As we use capacitor bank in 3ph ckt to improve PF, can we use capacitor in single ph domestric use, in house we have Fan,Mixer,electric cooker,iron,tube choke they also lag the system,because it is inductive load. if it is possible to improve PF of single ph system-- if yes- type of capacitor to be used,connection diagram, working in detail. if no-- list it.

1708


Differentiate between induced emf and self inductance?

1086


I have a CT meter with ratio 60/5. The meter reading of previous month was 3290.49 and that of current month was 3797.26. How many chargeable units as per normal meter should be my reading.

1361


how u select control transformer for a mccb panels or any panels?for expample we hav 440 volts maim supply and control volts is 230v?

2117


What is grid collapse? what is the reason for it?

2054


How can I calculate ISF of current transformer?

3557


what is the meaning of osr in transformer.

2051


what is the circulate the diesel in DG in side pls tell parts name and picture with circulate the diesel

1940


Why 9KV surge arrester having 7.65KV of MCOV?

1517


How much load can take a 16 mm aluminum cable 3 phase

1700


how we calculate electrical load on a building according to area?

2729