we are used SAMSON 3730 Smart positioner.please tell me how to calibration this.

Answer Posted / chanchal

at first check the air supply.if it is ok then
feed the 4mA by using calibrator in i/p converter of positioner. if valve is zero position(fully closed) then its ok.if valve is not in zero position(fully closed) then set the zero position in positioner by using zero point screw.
next feed the 20mA by using calibrator in i/p converter of positioner.if valve is 100% open then its ok.if valve is not 100% open. then adjust the span setting by using span screwin positioner.
then check 25%,50%,and 75% open position in valve by feeding 8mA,12mA,and 16mA by using calibrator in same way.

Is This Answer Correct ?    4 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the importance of CV in the control valves? how it is calculated?

1968


how u choose thermowell lenght n pnumatic C/v size?

1675


Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell

747


how the arrangement of equipments done in control room

1596


what is the reason while warning lamp is on while the engine is cranking?

1629






I want to know the questions asked in ONGC interview(after being selected in the written exam) for Instrumentation branch.Kindly help.

1766


Give an example where you had aproblem on the job, and tell me how you solved the problem. and the finalvoutcome.

1815


components of control circuit belongs to control valve

1243


HI friends.I am Surya a BTech in Electronics and Instrumentation Engineering.I am going to appear Relince Industries Ltd all India writen test very soon. so plz help me by sendind the probable questions about my subject.My mail ID is surya.barik@gmail.com.

1789


what is a half wave, full wave, and bridge rectifer.

1263


please tell me what is a light up procedure of Cfbc boiler and what it's axuillaries of cfbc boiler?

8215


What is the exact differences between HART,FOUNDATION FIELDBUS,PROFIBUS?

3010


whats the abbreviation of IOP? is it instrument of power or input open problem?

669


why use 50% lel methane gas concentration for gas detector calibration instead of 60% lel gas concentration whereas the hi alarm set at 60% lel.

2211


Explain PID controller tuning & any one method used for it.

7012