Answer Posted / harshad
First calculate the current.
Eqn for 3phase: Current= Connected load in watt/sqr root of 3*415*pf
Eqn for 1phase: Current=Connected load in watt/230
Select the cable size from the chart with respect to the current.
pf(power factor) is 0.8 or 0.9
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Is it acceptable of installing an earth pit in planters area where bare copper cable, earth rod and connection are susceptible to corrosion due to water?
solar inverters was not connected to the nuteral link .this nutwral possible to any other systems
what is gridrotor resistance starter
What are the difference between normal application Transformer and Solar application Transformer?
Which power will flow first if we switch on a motor Active or Reactive? How?
what is the difference between oil surge relay and buchholz relay.
How we calculat the NGR of 3phase Generator, Our generation voltage 11KV
What is the direction of current flow in ct secondary...means if the current is flowing from P1 to P2 then what will be the direction of current flow in ct secondaryw
How can ou verify the size of conductor 50Sq.mm ACSR
Why a Permanent Magnet Generator has higher frequency as compared to frequency of main alternator?
I am doing apprenticeship training at HT switch yard in NLC. How can i get electrical c license. ??? What r the rules for getting it as an apprentice? ??
What is the difference between solid grounding and impedance grounding?
why don't we use the generator as a motor? and what will happen?
What will be the voltage regulation of a full load and 0.80 power factor lagging load transformer when a two winding single phase transformer has a voltage regulation of 4.5% at full load and unity power factor?
how withstand of hi-pot test outputs of transformer wire 2.5mm