the total iron closs in a transformer core at normal flux density was measured at 25hz and 5ohz and was found to be 250w and 800w respectively.the hysteresis loss at 50hz would be................?????
Answer Posted / utkarsh agarwal
according to the data flux density is constant.
Pe1=f1^2 Ph1=f1
Pe2=f2^2 Ph2=f2
takinf f1=25hz
f2=50 hz
Pe1/Pe2=1/4
Ph1/Ph2=1/2
now iron loss Pi=Ph1+Pe1
Therefoe
1. ph1 + pe1=250
2. 2ph1+ 4pe1=800
solving we get ph2= 200w
P.S. : "=" is meant to be proportiaonality sign in first 3 lines
| Is This Answer Correct ? | 8 Yes | 1 No |
Post New Answer View All Answers
how to design step down 12 V, 1mA small transformer from 220 V AC? Because according to VI relation and power transfer it results bulky...
What are the different methodes for calculating the short circuit Current?
In motors how many types of cooling systems were used?
what is the function of bearing in dc mchine" and where it is placed
What is the rate of WCT on the Electrical Contracts comprising of DG Sets and Civil Works in Delhi ?
what is the principle of operation of tungstun bulb ??
how to select the automotive wire size by mathematical calculation. for xenon headlamp with ballast. the ballast given data voltage 10-17v,current permenant 6amp, run up phase is 15amp, peak at swicth on max 400micro sec is 40amp.the sum of cable resistance is 150mohm.please provide referenc document if any for relating the peak at switch on current,time & wire wire size
can we conduct the swineburne's test on a dc series motor? why?
Can Anyone suggest the Standards (IEC or IS) for selecting copper current density?
How to calculate the volumetric capacity of a oxygen & Nitrogen gas Cylinder if pressure is 145 kg/cm2 & water capacity of cylinder is 67 liters.
explain Density
How can find thermal state value in relay for calculate thermal overload.
how we can come to know that motor winding resistance which showing by DMM is right or wrong???is there any chart or something that we will compare & check???
What is the automatic voltage regulator with servomotor?
how to changeover ups in this power failur time?