Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

my temperature transmitter in field showing 700 degree , whereas in dcs showing 459 degree, how to resolve this?

Answer Posted / carl_ellis

1) Most likely, the 4-20mA scaling (what the 4-20mA represents) is not the same on the transmitter as it is on the DCS.

The scaling has to match, that is, be the same on both the transmitter and the DCS analog input.

2) A ground loop will cause an offset. The offset can be negative or positive, depending on the polarity of the ground loop.

Eliminating ground loops can be a major task, so most times, a loop isolator is used to isolate the transmitter from the DCS, which eliminates the ground loop.

Carl Ellis
Measure First

Is This Answer Correct ?    5 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.

2716


Q-Explain the different load conditions that will produced different offset which may or may not be acceptable to thhe control function

2140


i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....

1414


PLEASE PROVIDE SAMPLES OF CHEVRON SKILL TESTS

3854


how do we commission inergen system?

1897


How to calibrate Field bus transmitter? procedure ?

2281


Good evening all I need a small favour regarding reliance paper i wanna probable sample papers(e&i) of reliance. if any of u have any idea about dis then plz mail me back.i belongs to electronics and instrumentation engg.so i need e&i papers. thanking u....

2034


How to calibrate displacer type level transmitter (chemtrol make )for level measurement in hotwell , LP & HP heater ?

5864


SOME OF YOUR QUESTIONS ARE NOT MAKING ANY SENSE SO TRY AND PUT IN A LITTLE BIT MORE EFFORT BEFORE YOU POST A QUESTION. WE WILL ONLY HELP THOSE WHO WE CAN SEE ARE TRYING TO HELP THEMSELVES.

2310


Give 2 application of quartz crystal used for process parameter measurement.

1972


in natural gas indirect water bath heater,how to prevent the problem of backfire from firetube during ignition...becoz of this backfire performance of wbh is going low.

2751


WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?

2478


why fuse block is not used for AI signal?

1828


What is the diffrence between ff tx and non ff tx

3129


Describe how to use megger to measure the earth resistance and insulation resistance

2165