my temperature transmitter in field showing 700 degree , whereas in dcs showing 459 degree, how to resolve this?
Answer Posted / carl_ellis
1) Most likely, the 4-20mA scaling (what the 4-20mA represents) is not the same on the transmitter as it is on the DCS.
The scaling has to match, that is, be the same on both the transmitter and the DCS analog input.
2) A ground loop will cause an offset. The offset can be negative or positive, depending on the polarity of the ground loop.
Eliminating ground loops can be a major task, so most times, a loop isolator is used to isolate the transmitter from the DCS, which eliminates the ground loop.
Carl Ellis
Measure First
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.
what deference between panel earth and systemearth
There are two chlorination tonners both are connected to two pressure swithes and the pressure switch is connected to SOV which operates the valve to changeover the tonner selection i.e if pressure one tonner goes low the other tonner should come in line if it is inautomatic selection design a circuit using relays ?
Sir , i have completed my M.Sc In Instrumentation and presently working in Maintenance department 3 yrs Exp , is there is any possible for work in offshore ..
What is difference between ESD and PLC please Explain me clearly.
in valve is constructed as per SME B 16.34, then which standard is used for fire testing of valve?.
what is droop in governer ,type of droop ,how it work
describe flow nozzel principle?
Linear amplifier.
what is your eligibility criteria for freashers?
Valve positioner and actuators in detail.
What are the maximum packet size of: a) HART b) Profibus DP c)Profibus PA d) DeviceNet e) Foundation Fieldbus
model question paper of instrumentation for Jindal GET 2010.plz reply sudhanshukumar08@yahoo.com
Why is it necessary to use compensation leg to measure the liquid level in a closed or pressurized tank?
How many types of sensor