When alarm is activated in buccholz relay in transformer
Answer Posted / spl
Depending on the model, the relay has multiple methods to detect a failing transformer. On a slow accumulation of gas, due perhaps to slight overload, gas produced by decomposition of insulating oil accumulates in the top of the relay and forces the oil level down. A float switch in the relay is used to initiate an alarm signal. Depending on design, a second float may also serve to detect slow oil leaks.
If an arc forms, gas accumulation is rapid, and oil flows rapidly into the conservator. This flow of oil operates a switch attached to a vane located in the path of the moving oil. This switch normally will operate a circuit breaker to isolate the apparatus before the fault causes additional damage. Buchholz relays have a test port to allow the accumulated gas to be withdrawn for testing. Flammable gas found in the relay indicates some internal fault such as overheating or arcing, whereas air found in the relay may only indicate low oil level or a leak.
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What is meant by load angle of an alternator? Upon what factors does the load angle depend?
sir& friends i want the collection of recent quetions asked in interview of top most companies please send me on my email san.jsr@hotmail.com
what is negative d.c. voltage, why this voltage is used in base transciever station.
can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?
what is the method of earthing of a transformer using electrodes?
Describe Non I.S. Earth System and why is it used?
defination of lines
After synchronization with grid what is the demand value QKVAR and how we will maintain that?
how to build a network which step down 415v to 1v rms
How to use earthing on shipments.
what are the main applications of transistor in non-linear region?
what is the power factor used by the PHCN in nigeria? 2. what is the difference between an alternator and generator. 3. Generation of poweris in KV but how is transmission is in MW. 4.If the transmission of power is 20,000MW how can it be increaesed to 80,000MW
What are the different sign conventions used in electric circuits?
What is difference between Sample test and Routine test in safety standard?
what is the terminal voltage of dc series generator running at rated speed at no load?