Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I want to know which cable would be best to carry 125A current to a distance of 50m. Voltage is 3phase.
Kindly share the formula with answer.

Answer Posted / sudesh

according to IEE regulations recommended voltage drop is 3%.
voltage drop=(400x3)/100
=12V
if we select 35sqmm pvc/xlpe/cu cable, it can carry 158A max.current.
so now we should consider about voltage drop of cable.
true voltage drop=volt.drop for cable*Current*Distance
=1.15mV/A/m * 125A * 50m
=7.18V
7.18 < 12
so 35sqmm cable would be best to carry 125A current.

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

in an electronic tri vector meter when the current and voltage sequence changes ? what is the effect of phase sequence on recording of meter

2234


what is through fault?

2286


What current flows in the transformer primary when its secondary is open?

1258


what is the profesional board for electrical engineer what is thepast and during construction for electrical engineering

2069


hi I have done 3 yrs diploma in electrical engg after 10+2. I have 16 years of work experience into design proposals sales and engg application development in LV/MV swithcgear and sub station automation field. I want to apply for immigration to new zealand but I am not sure whether I qualify or not since I dont have a degree. Can anyone advice? Thanks Riz

2285


Practical condition in 400KV Sub station:- Breaker(open) , isolator(open), Earthing (close) at both end e.g A & B. Now Open A Stn Earthing than Open B stn Earthing (Which have a 50MVA reactor) , AND suddenly show R,Y,B phase 704KV,573KV,118KV respectively. Que is without closing of breaker how it is possible.???? My Whats app No:07621840498 for Further Discussion. Pls experts suggest.

2090


why voltage form factor of PT are increase , when it is ecpected heigher spikes in system. how it is calculated.

2139


what is the practical application of full adder circuit?

1857


Explain what is rated speed?

1135


how to find the resistance and gap volatage of the diode??

2058


what is active power & reactive power?

2191


Explain how you intend to work under pressure to meet up with deadline target?

2393


why connecting surge unit in contactor coil

1889


Where can I get CPWD electrical specifications & Shedule of rates? Please help me

2258


I am a possesor of c licence from 1993. I forgot to renew during the year 1998. During that time I was working at TNEB to till date. Is there any possibility to get renewed? or to apply for a new one?

2040