Answer Posted / s kannan
MF is not for panels for relays and meters only. Meters will be connected with CT and PT's secondary. If we want to calculate MF for meters like Voltmeter and Ammeter Just follow the formula Mf= CT Ratio X PT Ratio.
Eg:
CT Ratio: 600-300/1-1A(Adopted ratio is 300A as primary) PT Ratio: 33KV/rt3/110V/rt3/110V/rt3
Then MF:(300/1)X(33000/rt3/110/rt3)
(300/1)X(33000/1.732X1.732/110)
(300)X(33000/110)
(300)X(300)
90000
Means Multiply the particular meter's reading by this 90000 for obtaining the genuine value.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how we decide the require size is this for a known current at fuu load?
Why air circuit breaker off due to power failure?
What is the Load Capacity of Panther conductor (0.2) and dog conductor (0.2)
physical identification of HT & LT panel
can we synchronize star system generators with delta system transmission line ? and how ?
If VFD is On but no starting commond on it. so how many outpout voltages of VFD
Showing results for capital, machinery, stock,wages, carriage in words, salaries, factory rent, repairs, fuel and power, buildings, debtors, sales, purchases, creditors, return outwords, return inwords, drawings, discount allowed, discount receivable, office expenses, bills payable, bills receivable, cash in hand, cash at bank, office rent comes under debit or credit
Hi.. I am a BE GRaduate in E&E. I have 8.5 Experience in Tendering & Estimation field. I have done SAP SD course few years back. But due to some reason i failed to get job in that field and continued my own field. Now I am thinking of changing into SAP seriously. How should i go ahead???
i ha done my 10th with 71% ,ITI with 81% 11th with 75% 12th 43% apprentiship with 71% in SAT i secure 1390 ,TOEFL 27 i was refused four times and in all me interview visa officar told that i am not Qualify for study in USA but i completed my 12th yes i got low persentage in my 12th but i seen to much student they already got visa with them 3 or 4 backlocs so why they are refused me ?
what is 3rd Harmonics? how it is generated in alternator
I have a small system with two motors that are running on 380 vac, 60 hz. These motors are expensive and I usally get them from Brazil. I am adding another motor to the system, but I want to purchase a 480 vac, 60 hz motor to use. It will be on a VFD that is rated fro 380 thru 480. Is this posible and will I have to use a larger motor and derate it?
where lt & ht capacitor used
how synchronous condenser is used in place of synchronous generator with out negotiating IEEE standards? Can i use 3 generators as synchronous generators and 2 generators as a synchronous condensers in an IEEE 14 bus system with out disturbing the standards?
in electrical control panel. how can i choose the cable rating. (example - 11kw motor, 18-25A mpcb}
when 20hp 3 phase motor start no load condition in star or delta connection.find current and write formula.(tariq)