A LT ckt i mean 440 volt flow of current100A.at this time HT current what will ON 11 KV &33 KV.plz givemy answer with example
Answer Posted / s b mutha
Voltage Ratio : 11000/440= 25, 33000/440= 75
So, current in primary will in 11KV= 4 Amps and in 33KV= 1.333 Amps
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
List the advantages of star-delta starter with induction motor?
What types domain of laplace transforms? What behavior can laplace transform predict how the system work?
how we can calculate power factor in single phase & three phase ?thank u
What Should be the value of Vector Surge angle at Tripping and how to calculate it?
how to select the automotive wire size by mathematical calculation. for xenon headlamp with ballast. the ballast given data voltage 10-17v,current permenant 6amp, run up phase is 15amp, peak at swicth on max 400micro sec is 40amp.the sum of cable resistance is 150mohm.please provide referenc document if any for relating the peak at switch on current,time & wire wire size
how to setting Load amps tripping time and extra settings for load Transformer protection relay with RMU panel using C&S model relay..?
why the carbon brushes are broken in srim while the motor runningtime
What is size 00, 01, 1 etc., in HRC fuse types?
we have an energy meter in a capacitor bank panel, So should we consider it's readings as energy consumption on daily basis. (when capacitor bank doesn't have any energy losses)
What are the applications of autotransformers?
Difference between earthing & grounding.?
i applied for the ap transco please forward the freqventley asked QA
What is ideal IR values for ground and neutral.
Hi,I am working in abroad for more than 3 years in a company operating with 11kv and 6.4 MW power. I need c licence in India,can I? some other says only i can get if i work for 2 years in india only! anybody kindly clarify by doubt.Thanks
What is acsr cable and where we use it?