Where should we terminate the shield and why?
Answer Posted / carl_ellis
Shielding reduces electrostatic or capacitive coupled electrical noise in signal or communications cable
Electrostatic or capacitive coupling is proportional to the capacitance between the noise source and the signal wires. The magnitude of the interference depends on the rate of change of the noise voltage and the capacitance between the noise circuit and the signal circuit.
Electrostatic noise can be addressed by installing an electrostatic shield (also called a drain) around the signal wires. The currents generated by the noise voltages prefer to flow down the lower impedance path of the shield/drain rather than the signal wires.
The shield/drain must be of a low resistance material such as aluminum or copper. For a loosely braided copper shield (85% braid coverage), the screening factor is about 100 times or 20 dB. For a low resistance multi layered screen, this screening factor can be 35 dB or 3000 times.
The shield should be insulated to prevent inadvertent contact with multiple ground points, which could result in circulating currents.
The shield should never be left floating because that would tend to allow capacitive coupling, rendering the shield useless.
A single point connection to ground attempts to minimize the possibilty of ground-loop current that will flow between grounds at different potentials. A shield grounded at both ends can form a ground loop which can cause a processor to fault if those grounding points are at different potentials.
Vendors may specify grounding the shield at either the field end or the receiver end. When the shield/screen is grounded at one end only, the grounding is usually made in equipment panel/cabinet at the end with the power supply or the receiver. The field device end is left ungrounded and the shield/screen insulated.
At sites with equipotential grounding where the grounding is the same potential between grounding points, some vendors (Profibus DP's RS-485) recommend grounding the shield at both ends.
Cabling that runs through intermediate junction boxes shall have the integrity and continuity of shield connection maintained in the junction box without connecting the shield to a ground in the junction box.
The signal wire shield is never connected to the common side of a logic circuit (this would introduce noise into the logic circuit).
For high frequency RF noise rejection, a capacitor is inserted in series between the shield's drain wire and the ground connection.
For some communication network cables, the shield connections are unique to the particular cabling system. In some such cases, a dc short to ground is not needed because a low-impedance ac path to ground and a high-impedance dc path to ground are provided internally at each node. Follow the specific instructions in the publication provided for the specific communication network cabling system.
At any shield grounding connection, do not strip the shield back any further than necessary to make a connection.
Carl Ellis
Measure First
| Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
Somebody tell me in what way i need to prepare for csio pgrpe(adv instrum eng)interview?what all the quest can i expect?
What is mean by analytical instrumentation?
please tell no. & add. of consultancy who recruit me in power plant as instrumen engg. present i m working in power plant as ass.t instrument engg. thanku mahesh 09226562826
What is the differerence between hysterisis and linearity.
what is the diffrence between pressure safety valve & pressure relief valve....pls
please tel me the calibration of pneumatic controler.
Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com
Instrumentation Safe Guarding test. How to determine the interval time of the test. eg:Halfyearly,Every year,Every three years etc.
can anyone tel the syllabus or previous year question paper for BHAVINI(EIE)2014.
full process of gas turbin?
What materials are used in thermo wells?
what is loop1 and loop2 in MTS LT?
What is super thermocoupal?
How does temperature bath work? How does coil gets heated only by applying some current?
What is the diffrence between ff tx and non ff tx