Can a 50-Hz designed transformer be used at 60-Hz system?
Is the same remains true, when a 60-Hz designed transformer
be used at 50-Hz system? Consider only frequency variation.
The voltage remains as rated value in all cases.
Justify the answer.
Answer Posted / brajeshjhaa
For a transformer the voltage is proportional to the product of flux and frequency.
case-I
Voltage = constant
Frequency = increased from 50 to 60Hz i.e. change by 120%
For Transformer:
Voltage = flux * frequency * K; k is a constant
so when frequency increases by 120% flux decreases to 83.3% Now;
Hysteresis loss = flux^2 * frequency^2 * T; T is constant
At 50 Hz
Hy. Loss@50 = flux^2 * Frequency^2 * T
At 60 Hz
Hy. Loss@60 = (.833flux)^2 * (1.2Frequency)^2 * T
On evaluation:
Hysteresis loss@50Hz = Hysteresis loss@50Hz
Eddy Current Loss
Eddy C. L. = flux^1.6 * f * C; C is a constant
Eddy@50 HZ = flux^1.6 * f * C
Eddy@60 Hz = (.833flux)^1.6 * 1.2F * C
On evaluation;
Eddy@60Hz = 0.895 * Eddy@50HZ
So it is seen that a 50HZ transformer when operated at at 60Hz has same hysteresis loss eddy current decreases. As the core loss decreases the transformer can be safely operated.
But if a 60Hz transformer is operated at 50Hz, then just the reverse of above the core loss i.e. eddy current loss will increase and hence the core loss will go high; hence not advisable to operate.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Give the expression for the frequency of oscillations in an op-amp sine wave oscillator?
Circuit diagram of tube light without starter using electrical choke
11 kv input, 66 kv input advantages
is it possible to turn on the single phase star delta on delay timer using 24 v dc ?
how to carried out tan delta test in 11 KV alternator ?
What is a dc motor?
What is Anemometer used to measure?
On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?
how to calculate the torque of a motor?
Why we make earth connection with Transformer Body and What will be the minimum size of copper wire as per code with respect to KVA rating of Transformer?
what is the acceptable value of TAN DELTA and dissipation factor for 11kV, 1.75HP Motor?.
What is the different types of cable & current capacity of cable
sourse is 66 KV / 350 MVA, transfarmer is 1000 KVA 6.6 / 0.415 kv, iF fault is 28.75 MVA on 0.415 KV Bus then calculat the Transfarmer Impidance
what is sevice settings for mccb?How can be it setted?
What happens if the series current double?