what is difference between 3.5 core and 4 core cable

Answer Posted / kapil tayade

3-Core Cables

These cables are used generally for a perfect balanced 3-phase system. When the currents on the 3-live wires of a 3-phase system are equal and at an exact 120° phase angle, then the system is said to be balanced. The 3-phase loads are identical in all respects with no need of a neutral conductor.

An important example of 3-phase load is electric motor and that is why, they are fed through 3-Core cables in most cases.

3.5-Core Cables

A 3-phase system may have a neutral wire. This wire allows the 3-phase system to be used at higher voltages while it will still support lower voltage single phase loads.

It is not likely in such cases that the loads will be identical, so the neutral will carry the out-of-balance current of the system. The greater the degree of imbalance, the larger the neutral current.



When there is some degree of unbalance and the amount of fault current is very small, then 3.5 core cables are used. In these types of cables, a neutral of reduced cross section as compared to the 3-main conductors is used, which is used to carry the small amount of unbalanced currents.


4-Core Cables

When there is severe out-of-balance conditions, the amount of fault current will raise to a very high level. Generally in the case of linear loads, the neutral only carries the current due to imbalance between the phases.
The non-linear loads such as switch-mode power supplies, computers, office equipment, lamp ballasts and transformers on low loads produce third order harmonic currents which are in the phase of all the supply phases.

These currents do not cancel at the star point of a three-phase system as do normal frequency currents, but add up, so that the neutral carries very heavy third harmonic currents.

Is This Answer Correct ?    20 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHAT IS THE MEANING OG (li = 7 In)

1535


tell me about roaster switch .& what is the function in transmission & distribution?

2172


How harmonic block test are conducted on relays ( Siemens,Areva ect )power transformer using omicron kit?

1759


what is ps impedance test

1662


Difference between shunt, PMG and AREP excitation. Which is the most reliable between PMG and AREP.

9021






how to increase senstivity of ct

1928


I have 4 busbar of 1000 ampere. we use 4 busbar to make 4000 ampere in one phase.my problem is that when we applied 60% load on that then busbar produced high noise.what is the reason of that and how can i minimize that noise.

1295


Electronic circuit

610


How we select the vector group of 3phase power transformer?

1988


What are the different types of hydro schemes?

673


why are u join ntpc

1731


different aspects of voltage stability

1538


i want design of D.C.MOTOR 1HP 960RPM AND 2HP 960RPM ITS URRGENT

1556


what is the difference between electrical and electronic choke?

1477


How much pf maintan in dg set in 6o% load,when Dg runnig Neutaal Earthing removed what happen.

1529