under which situation or why restricted earth fault protection operates in out side its zone that is external fault

Answer Posted / hg

1) if any one ct saturates at through fault current due to
a) high harmonic content of current in through fault current leading to high voltage appearing across secondary and the ct saturates

2) under above scenario if there is no stabilizing resistor/ damage to stabilixing resitor than relay may operate

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

can dp type level transmitter work in under vaccum condition

1533


dear sir i have completed one year post diploma certificate in thermal power engineering from national power training institute durgapur ...plz suggest me for power sector job

2070


Why superheated are started before I'd and rd fan?

1692


what is natural frequency of turbine shaft .

1720


LAPT working in alternator / generator

2544






what is the basic use of power plant in equipment

1225


explain how the third harmonic content of the magnetising current affects transformer design

2770


can u please tell me how to calculate the concrete quantity for a under reamed pile? r=300mm,depth=3m for a cylinder and for bulb l=.750mm,width=.525

1278


why airtel use + 24 volts and other operators use -48 volt

2106


How do you consider that you can improve and what assistance do you need to achieve this

1332


why do you consider yourself a suitable candidate for this position

6977


why is the in steam turbine axial displacement of active side thrust pad is positive and non active side thrust pad is negative.

2762


some one can tell me how residual type excitation is provided through transformers to an AC generator without any battery or PMG&excitor

1948


how to differentiate between "ALL fuel lost" and "All Fuel Lost" in Boiler MFT condition?

1228


What is LB-SR.

2483