how to calculate the multiplication factor in HT incomer
trivector meters
Answer Posted / ripun
Mf=field ct ratio/meter ct ratio *field pt ratio/meter pt ratio
Let field ct ratio=15/5a
Field pt ratio=11kv/110v
Meter ct ratio=-/5a
Meter pt ratio=-/110v
M.F=15/5*1100/110=300
Is This Answer Correct ? | 21 Yes | 15 No |
Post New Answer View All Answers
Draw a 230kv two-bus bar system showing the following. 1.Two generators (150MW) each connected through one 15.75/230KV transformers 2. 1 outgoing lines 3. Two 230/130 KV transformers 4. BUS PT's 5. CT
how to determine motor size for a fan application?
define superposition theorem thevnin theorem ,norton theorom?
Differentiate between voltage and current feedback in amplifiers?
Some times to change of DOR of a motor, interchange of R & B is not effected and RYB take same current, but interchange of R&Y is effected ie change the DOR. My doubt is what is the problem in motor and how it is happen.
what the Microsoft .NET framework is?
what is a vector protection in transformer
what's prime importance of protection in electrical system.if protection system don't work properly what can happen in electrical system?
What is the formula to calculate distribution transformer De-rating on iron losses basis
What are electric motors?
what is the function of anti pumping relays? what is KVAR? How it is generated in alternator? What is 3rd Harmonics? What is IDMT relay?
What is meant by derating factor?
we have require a Motor (1500kW, 6.6kV, 50Hz) which shall operate at 1500rpm during 30min and after it shall run on 500rpm during 15min. The same cycle shall be repetitive during the whole working days. Which method is best and economic to achieve such type of task. VFD, VVFD, Pole changing motor etc.
Has someone here done a sizing for a generator (3 phase), its for a pumping station. If you have an example for standby/duty and both running (I) star delta (ii) Soft Starter.
at what basis/standard we have to arrive the current density of aluminium/ copper in busbar?