Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Is it possible to run HT motor through LT VFD (LT VFD supply given to Transformer LT side and transformer HT side connected to motor)

Answer Posted / kingshuk dey

To start with, let's get our concepts correct. The motor supply comes from the VFD, which in turn is connected to the power supply from a board (or LT side of transformer, in your case).

Supply(TRF) --> VFD --> Motor

First off lets assume your VFD type is less than or equal to this LT supply. (LT/HT for TRF is subjective, Lt can be 220V when HT is 460V, or 460V when HT is 1000V etc). But a 460V VFD will burn its fuses if connected to 1000V.

Anyway, if you connect the VFD to LT side, and the motor is HT (meaning it's rated for a heavy current like 32KV), the motor will try to pull more and more current to start from the VFD, ultimately exceeding the current setting of the VFD and it will trip with an Overload or Overcurrent (OH, OC) fault on its display. If the current is enough to start the motor, it will rotate, but with very less speed (like if the motor is not connected to any load).

Just as a matter of interest, if you connect the LT side of TRF to VFD, and HT side of TRF to motor, "nothing" will happen as there is no current source (both VFD and motor are current consuming equipments) :P

Motor --> TRF HT -- TRF LT --> VFD (LOL!)

Is This Answer Correct ?    1 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the drawback of static coefficients?

1608


how can we select the type of wire.what factors we have to look on it , do we have some formula to calculate it. please guide me on it

1939


In PFI plant one stage capacitor connection is directly connected(with out megnetic contact controll). but why?

2287


If I want to replace a 26KW Slip ring Motor with a Squirrel Cage motor & Drive (for a Hoist Application). How can I approximate the Motor & Drive HP required in new Setup.

2265


Dear Brother can u tell the proper size selection of cable & the fault level calculation of braker, busbar etc. pls mail me at azeemk30@gmail.com

1925


DEAR SIR/MADAM,CLEARLY EXPLAIN ABOUT CRAWLING AND COGGING EFFECTS IN INDUCTION MOTOR.

1894


why occ characteristics curve in not tracing back when we are bringing back the rhoestat?

1860


Air refrigeration cycle works on the

1090


how we can do the insulation on secondary of ct explain and so that tan delta will within limit

1924


What is the complete procedure of erection of electrical panel in industry

1860


why ups rating in kva? and why ups are in parellel?.why isolation transformer is used in ups?

1931


What is signal flow graph?

1100


Can you tell me more about pu systems (per unit systems )calculation in large power systems? how to get the base for voltage and power in generator, transformator and transmission lines?

2282


which pump used in STP

2208


What is the difference between resistance grounding system and resistance earthing system?

1079