Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

In dcs contol valve parameters showing like this












Gain=1 or 2 , ti=7 sec, td=20sec. But temp,pressure,level control valves we are using in which type parameter side using ti,td clearly tell me

Answer Posted / carl_ellis

Gain, ti and td are PID proportional control tuning terms/constants. PID controllers use PID tuning constants to calculate an output based on the error signal; final control elements (valves) do not do a PID calculation so valves are not involved with gain, ti and td. The controller is typically in the control room, the valve is somewhere out in the process.

A PID controller calculates the expected valve/damper position from the error signal and the tuning constants, the result of which is an output control signal ranging from 0-100%.

A valve positioner or valve I/P receives that control signal from a controller (4-20mA, Profibus) and supplies air or electric power to the actuator to achieve the correct position demanded by the control signal.

Ti is the term for reset or integration. It is used when the process itself is not an integrating process. Level, pressure, and pH are usually integrating processes. Sometimes temperature is an integrating process, sometimes not. When the process is non-self regulating/integrating process, the ti term is not used in the PID calculation.

Flow and temperature processes typically use the ti term for PID calculation.

An exception to the rule of PID being done in a separate controller is Foundation Fieldbus (FF), which allows function block PID execution in FF devices. In a case where PID control is executed in an FF valve positioner, then a valve would use the PID tuning constants.

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to calibrate Magnetic flow Transmitter in Field

1270


Why grounding is necessary? Give example with diagram.

2218


can anyone tell me about the basic concepts to consider before to start a PLC panel wiring

1938


What is the exact differences between HART,FOUNDATION FIELDBUS,PROFIBUS?

3468


define feed forward control loop with example and drawing?

3208


what is loop1 and loop2 in MTS LT?

4659


State bernoulli’s application.

1143


what is the difference between attemperator and desuperheater ?

5579


is motorized valve closed when power shutoff?

1734


what is the procedure of O2 sensor(ABB) calibration?

2187


what is sliding spool valves?

2236


how many type of plug are used in pneumatic control valve,name them.

5444


If i have 4 Allen Bradely make RS logix 5000 PLC and for viewing that we are using 4 RS view SCADA for 4 different packages. Now, I will want to view two packages on only one SCADA. Then how i will do it?

2385


What are primary elements of measuring pressure?

1283


How we can check the 2 wire proxy switch? & how it is connected to DI MODULE OF PLC?

2603