for a 11kv transmission line what capacity of CTs & PTs are
required?
Answer Posted / shivadathathri
11 KV CTs & PTs , Out door Pedestal mounting versions will do. Current ratio , STC Rating & Insulation level can be determined with connected load. Like breaker / Transformer Etc. Example : Load is 11KV 100KVA transformer is connected . Then use 11KV Cts CTR: 5/5 Amps , Class 0.5 for metering , Class : 5p10 for Protection . OCF - 150XI nominal . Oil cooled CTs for MUSS. If it is mounted inside panel / Control room then Use Resin cast type. SHIVADATHATHRI- 9632153842.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what are the major & minor faults that occur in an inverter and in UPS ? And how to repair and resolve them ?
what is meant by brushed alternator & its working principle ?
what is apparent poewr, reactive power, & active power?
how to select proper cable for ct wiring so that drop within the limit.
how much value of resistance should connect to 15 kw, 6 pole 3 phase slip ring induction motor having RV-240, RA-42.
What is the difference between a 3 winding and 2 winding Potential Transformer
for opening electrical shop, tips needed.
in my working site. momentary jerck in electrical supply ocurred frequently which cause of multiple losses in our electrical equipements. how can we protect our electrical machines and equipements in this situation.
Initially, when the input is not equal to the output — what type of response is this?
tell me about roaster switch .& what is the function in transmission & distribution?
we have provided 30 nos. relay contacts in panel.I want to know how do we do the numbering for the relay contacts as per any applicable standards
Generator,motor and alternator Working principal Please explain easily
Can we indroduce the principle of single phase induction mator to Transformer? i.e. by Producing rotating flux in the transformer.
why cable i burning without tripping. how can protect led street lights
grr resistance & contrator malt continuous