Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how the actually positioner of control valve working?
where we gave 3-15psi pressure to I/P converter where it is firstly applied ?- on I/P to positioner then what happen?
is control valve operate on 3-15 psi or its bench pressure?

Answer Posted / r_vaya

Valve Positioner actually working is following steps:
Supose valve is air to open and right now is at it's normal condition.at this condition positioner will not send any air to control valve.

Now given command to 10 percent to open 
So first positioner will send air strat to applying air to actuator ,when actuator will get sufficient air to perform operation it will start opening.
Now when the  valve will reach to the set point mean 10 percent,positioner will stop the air and maintain valve opening at a set point.
This thing is same in the closing

Thous positioner is works  to control the opening and closing .

 

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A flange is used for instrument connection for a system with a design temperature of 316C (600F) and a design pressure of 1000 kPa (145 psi). What is the class rating of the flange to be used for this application? Explain your answer

2652


WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?

2137


I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration  So is there any causes biside this or  any  permissives ?

1858


In control valve proximity inductive sensor is taken as digital feedback for full open and full close.Normally its volts 24v when the sensor acts the feed back voltage 14v so that our relay not indicating in plc panel . kindly give the solution.

1978


How to fix back the valve actuator stem

2065


why we use 3 wire rtd direct wiring for temperature measurement instead of temperature transmitter like bearing temperature

1830


how we are selecting instuments by differentiating certain instruments in 4 to 20 ma range and certain in 1 to 5 v dc

2083


How can i copy program (parameter) from mm440 (V.F.D.) by using BOP?

2730


How many ohms are required for proper earthing?

1099


Hi, Is there any smart plant instrumentation design training institute in Bangalore?

1675


What inherent design and operating principles are included in a modern control system to use predictive maintenance practices to increase overall system reliability?

2100


Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com

1979


How flow can be measured with dp?

1146


What you mean by multi stage control vavles?

1813


why using negative supply for bentley nevada vibration system ?

2144