how the actually positioner of control valve working?
where we gave 3-15psi pressure to I/P converter where it is firstly applied ?- on I/P to positioner then what happen?
is control valve operate on 3-15 psi or its bench pressure?

Answer Posted / r_vaya

Valve Positioner actually working is following steps:
Supose valve is air to open and right now is at it's normal condition.at this condition positioner will not send any air to control valve.

Now given command to 10 percent to open 
So first positioner will send air strat to applying air to actuator ,when actuator will get sufficient air to perform operation it will start opening.
Now when the  valve will reach to the set point mean 10 percent,positioner will stop the air and maintain valve opening at a set point.
This thing is same in the closing

Thous positioner is works  to control the opening and closing .

 

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why we use cascade control and feed foreword control in 3 element control of boiler drum ?what is feed forward and cascade control system ?

1759


To become an Instrument DESIGN engineer, is there any softwares or training to become Instrument Design engineer, plz suggest me, Iam very much interested in designing.

2974


why we are using digital signals for I/O & how to measure this signals is getting or not ?

1547


how can leve transmetter calibate in feild .and also put cv and flow plz .....

1780


Why is the orifice tab provided?

715






pls provide me syllabus and old question paper of instrumentation engineering for GET(JSPL)

1854


the pump holds on run indication into the dcs and filed local control panel remote push button condition operaton wrong like when the push button pushing conditions the pump is off and the push button release condition the pump is on totally opposite condition . And control room inside give the stop command into dcs just 1secon relay engage and again normal condition. How can I slove

1136


Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?

1326


I am having a Phoenix digital to modbus converter. The o/p of the same is connected to flow computer FB407. But the digital signals are updated only after one minute in the flow computer. what may be the cause of delay in communication? Flow computer is having a scanning period of less than 1 sec.

1470


Full form of KKS when use DCS.

2616


what is IEC code in cables & how to selecting cables?

1295


WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?

1677


How does your previous experience relate to the job you are applying for ?

1565


There are two chlorination tonners both are connected to two pressure swithes and the pressure switch is connected to SOV which operates the valve to changeover the tonner selection i.e if pressure one tonner goes low the other tonner should come in line if it is inautomatic selection design a circuit using relays ?

1462


control panel design guidelines

2864