we met a disaster with our 62.5 kva genset, after rewinding
we informed by our contract engg that due to return current
coming in neutral & impropper earthing this happend.
But after all set up & load balance we checked & found
again we have about 20 to 32 amp return current on neutral.
we have 12 airconditioner + 12 mini fridge on single phase
line.
Pl suggest any idea to solved this problem
Answer Posted / sheikh
I think imbalance load is main reason of this problem and cross current compensation instrument transformer should be installed on your common bus bar to prevent this loss
but balance load all of 3 phase eleminate the highest neutral current.
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Can I use star delta connected induction motor for dual supply voltage?
For small size, high frequency coils, the most common core material is- a. )Air b. )Ferrite c.) Powdered ion d.) Steel
What will happen if we introduce negative feedback to a control system that uses a positive feedback?
In Electrical 'Single Line Diagram' cable nomenclature shows "2 X 1C X 630sq.mm to be provided for one incomer. The question is how many cable to be proved for one Incomer.
What is the resonant peak?
Why do we require transformer with less specific weight if supply frequency is increased?
Cb closed condition if there is a tcs fail whether cb will trip or not
what is the difference between earthing and unearth
Benifits of 3ph 4 wire metering over 3ph 3 wire
We have given to 3phase supply to ups system & how can coming netural
What are your future plans for the company if permanently employed?
why we cannot protect 100% winding of an alternator by using differential protection?
What happens if i apply 500V to 440V rotary Switch ?
What is EHT tariff or Power factor Tariff ????
What is Fire Panel ? How it works ?