My load is 15 kw,i want to improve power factor from 0.8 to 0.9,how select capacitor
Answer Posted / abdul rahman
Required capacitor KVAR :- KW X [tan cos (inverse(power factor old = 0.8)))-tan cos (inverse (power factor new = 0.9]
KVAR :- 15(TAN(C0S INVERSE (0.8)-TAN(COS(INVERSE (0.9))
= 15(TAN 36.86-TAN 25.84)
= 15(.75-.48)
= 15(.265)
= 4 KVAR
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
why do we use spark detector inside the slip ring brush compartment 0ona slip ring induction motor?
ow can i get certificate of competency as electrical supervisor and my diploma in electrical engineering from jalgaon.
IN dc capacitive reactance is??
What is Negative Potential Bias
why transformer ratings in kva? & DG ratings in kva? & Motor ratings in kw/HP?
what is resver in electrical enginnering with answer
advantages and disadvantages of inverse definite minimum time RELAY
What is the difference between cylindrical-type and sandwich-type winding?
what is lumped and distributed elements?
For electrical designers what are the standard should know? i want learn about this standards. how to get information/reference. anybody help in this regards please.
how to test the electrical panel.ht lt mcc pcc.
i have attended the interview on 4th June,08 at Kolkata in IOCL, can anybody tell me what is its result
In between UPS out going changer over switch and ups raising main input, both side cable gland producing heat but the cable doesn't get heat,Why?
Show the schematic arrangement of diesel power station layout and give its principle of operation.
The efficiency of a 100kva transformer is 0.98 at full load as well as half load , for this transformer what is the Copper loss at full load ?