we are use 130 hp load run with 0.98 power factor ( 38KVAR
capacitor connected ). if we need improve the the power
factor to 1 (unity). how much kvar capacitor to be add. have
any formula? please share with me.
Answer Posted / bmk mughal
KW=96.98
COS-1.98=11.470
TAN11.470=KVAR1/KW
KVAR1=19.69
COS-11=00
TANO0=KVAR2/KW
KVAR2=0
Required KVAR=KVAR1-KVAR2
=19.69KVAR
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
what is mppt (maximum power point tracking ) and how they used in solar power generation ??? what are the main components used in mppt?????
explain safety measures in alternator?
RATING OF LIGHTENING ARRESTER FOR 11 KV LINE IS 9 KV is ok ,but haw to calculate the KA rating?
if a 3phase 100kva distribution transformer , 400 v,50 hz, 4-wire system is loaded at 160 k.w mostly 1-phase Lighting & Airconditioning split a.c load what will be the net effect on the power system in terms of voltage, powerfactor, current , efficiency of xformer
How does a battary stores charge in it? please explain in simple manner and in detail.thanks
What are high pass filter and low pass filter? and What are the flowmeter ?
Could the power factor on electrical system can affect the registration of the kwhr meter or the CT/PT?
1)Explain why the cradle guard is used on railway crossing in overhead line construction?
List advantges of active filter over passive filter?
Why the earth to phase voltage is high 250 compare to other two phases
Which thing is maximum in RLC circuit at resonance a)power consumption b)inductive current c)capacitive voltage
how to calculate percentage impedence at 75 deg C at normal tap
- two pumps must work with them at the same time but if the first pump start the second pump must delayed for some time to start also , with motor rated power = 90 KW and rated voltage = 380 V and rated power factor = 0.85 lag please draw the power and control circuit for it and determine all circuit components parameters that you use it
What kind of preventive maintenance are there for transformer?
what will be the maximum winding temperature of 6.6kv HT motor 450kw, Full load current 49A. 50Hz Frequency.