Dear Friends,
Need your help for connecting APFC panel,
Quotation : I have 2 No’s 1000 KVA Transformers, both transformers are having separate APFC panels, ( Tr-1,400KVAR, TR-2,450 KVAR)
Now I want to stop One transformer, present load is 650Amps, Max, So One transformer is enough, I have switched OFF TR-1, but PF is not maintaining properly, its 0.5, So now I want to connect TR-2 APFC also in TR-1 Loads, Can any one answer for my Quotation with drawing, how to connect TR-2 APFC panel in TR-1 Loads,
Answer Posted / moh
Please use bus -coupler circuit breaker between the o/p of the circuit breaker TR1 and the o/p of the circuit breaker of TR2 with mechanical and electrical interlock between the circuit breakers.When one TR gone out the another TR will connect to another load and APFC by the bus-coupler circuit breaker. good luck
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
what is the difference b/w ATS and HTS?
What are the advantages of a three-phase system over a single-phase system?
700KW 6.6KV slip ring induction motor to use VFD to control the speed
what is accuracy ? in any meters , coils accuracy . how can u defined that ?
How many types oil using in transformer ? How many letars using in transformer..?
Can anybody please refer the best and simple book for about Protection relays and in detail of all its protection ?
Some times to change of DOR of a motor, interchange of R & B is not effected and RYB take same current, but interchange of R&Y is effected ie change the DOR. My doubt is what is the problem in motor and how it is happen.
who invented active elements? plz give me the complte details of active elements...
What the difference between three phase contactor (coil 110vac) & three phase SSR (control voltage 110Vac)? May I use contactor in place of SSR?
can indirect loading be called as phantom loading?
Explain in details how you would react to an unexpected incident when your supervisor or manager is not around to give instructions?
when will be the iocl interview results i faced interview on 8th september 2008 iam from electrical branch i faced interview for the post of electrical engineer??????????????????????//
Why does inductive loads consume KVARs?
what is draiv work
What is the function of under voltage release ?