Dear Friends,
Need your help for connecting APFC panel,
Quotation : I have 2 No’s 1000 KVA Transformers, both transformers are having separate APFC panels, ( Tr-1,400KVAR, TR-2,450 KVAR)
Now I want to stop One transformer, present load is 650Amps, Max, So One transformer is enough, I have switched OFF TR-1, but PF is not maintaining properly, its 0.5, So now I want to connect TR-2 APFC also in TR-1 Loads, Can any one answer for my Quotation with drawing, how to connect TR-2 APFC panel in TR-1 Loads,
Answer Posted / moh
Please use a bus-coupler circuit breaker between the circuit breaker of TR1 and the circuit breaker TR2 with interlock (mechanical or electrical). When one TR is out the another TR will connect to another load and APFC by the bus -coupler circuit breaker
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the formulae of Megger value for a A.C.Motor
it is possible to rotate the DG engine dc starter with wrong polarity connections? why?
(In MEP services) HVAC in AC Plant room what else can we provide if the chiller is not considered?
Can I use star delta connected induction motor for dual supply voltage?
Can Anyone Answer anyone of these ? Q1) why direct SOLUTION of Load Flow Studies in Not Possile ? Q2)Why majority of Buses in power system are load buses Q3)Why one of the buses in Power system is taken as reference bus (slack or swing) Bus ? Q4)Bus Admittance Matrix is a sparce (means it contains some zero elements ) matrix , give reason
Single line diagram for dbb (double bus bar)system.
How much costly in percentage wise is sandwich busduct costly than air insulated busduct of any rating?
please give me all the Alarm .Trip ,Safety Relays & Conditions of Chiller mail me on ashokbabunhce@gmail.com
What is the IS standard for MCCB to be use (As per capacity of AMP)& for ACB also.
How many kw will suply from one db
What current position are you holding in your current company?
what is buffer resistance starter.?.What is the working principle and where it is used..?
What are the parts in a inverter?
While testing a ZCT what parameters have to check or measure?
What is slip in an induction motor?