capillary type tranmitter using remote seals and capillary
tubes filled with liquid of known of known density so if
you wanna callibrate it just close block valve just before
capilary @ high side & connect druck apply it's calibrated
range pressure as normal calibration ensure low side block
valve must be closed & if you asking commissioning so this
is not a DP type pressure tx so simple if you wanna put in
servie this tx just open high side block valve & than low
side block
same way i do it but still transmitter showing -13 ma.just
tell me what i want to do ?

Answer Posted / carl_ellis

A 2 wire, loop powered transmitter can not output a negative current, like -13mA. The 4-20mA output is always positive.

However, a remote seal DP transmitter used for level will 'see' a negative pressure with nothing in the vessel and the LRV (lower range value) for the transmitter will be a relatively negative value, close to the (negative) span of level range.

A DP transmitter with remote seals used for level measurement will ALWAYS have a zero level reading that is a relatively large negative number because of the head pressure of the fill fluid in the capillaries.

The reason for the negative value is that the fill fluid in the high side capillary (which connects to the lower flange) pulls away from the transmitters high side diaphragm as it presses down on the lower seal by the force of gravity.

Oppositely, the fill fluid in the low side capillary (which connects to the upper flange) exerts a positive static pressure on the transmitter's low side diaphragm because the seal is up high and the fill fluid presses down on the low side transmitter diaphragm, again by the force of the acceleration of gravity.

A differential transmitter works by subtracting the low side pressure from the high side pressure:

High side minus low side = differential

As an example, in a vessel 7m tall, the transmitter has two remote seals, each 4 meters in length. The upper seal has to be above the liquid level in the head space above the liquid. The medium is water, SG = 1.00.

Assume a fill fluid with a Specific Gravity of 1.00, 4m of high side capillary and 4m of low side capillary. With nothing in the vessel (zero level), the applied pressures would be:

high side pressure = approx - 3.75m H2O (negative 3.75 meters, water column)
low side pressure = approx 3.75m H2O (positive 3.75 meters, water column)

high side minus low side = differential
-3.75m minus 3.75m = - 7.5m (negative 3.75m minus 3.75m = negative 7.5m)

The LRV (lower range value) would be approximately -7.5m H2O.

The transmitter needs to be ranged properly, with the appropriate lower range value for zero level.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

I want to apply for the universities in US,but i got the GRE score of (650+300=950)TOEFL 69/120.Is this score sufficient for applying universities please i am married i need to go to US because my husband didn't get H1 yet.please send me suggestion

1634


How will you calibrate PID controller? explain with example.

2113


why I need valve guard and whats different between guard and positioner ??

1050


Linear amplifier.

1715


what is the minimum power (P=VI)to produce a spark?

1699






draw shematic diagram of c/v positioner(smart type)?

1956


what is the diffrence between pressure safety valve & pressure relief valve....pls

1928


Define the difference between a stable versus an unstable controlled system and some of the tools you might use to be able to detect when this is happening and assumptions used for control system application design that could contribute to instability

1564


how to connect transmitter measuring sulfur process? 1-by using long impulse line or 2- by using coated short impulse line

1794


hey any one got the papers of SAIL and HPCL plz do help me by posting them to my mail ID's naren07_87@yaho.co.in, surenarendra@gmail.com

1673


How to Calibrate Ultrasonic Level Transmitter in field

988


What are the application of bernoulli’s theorem?

837


what is cold loop? difference between hot and cold loop?

1909


WHAT ARE THE INSTRUMENTAL DIAGRAMSOF VALVES?

1864


How you calibrate absolute pressure with the calibration range of 0 to 1000 0C Absolute. Please explain the procedure for calibration.

1434