capillary type tranmitter using remote seals and capillary
tubes filled with liquid of known of known density so if
you wanna callibrate it just close block valve just before
capilary @ high side & connect druck apply it's calibrated
range pressure as normal calibration ensure low side block
valve must be closed & if you asking commissioning so this
is not a DP type pressure tx so simple if you wanna put in
servie this tx just open high side block valve & than low
side block
same way i do it but still transmitter showing -13 ma.just
tell me what i want to do ?

Answer Posted / carl_ellis

A 2 wire, loop powered transmitter can not output a negative current, like -13mA. The 4-20mA output is always positive.

However, a remote seal DP transmitter used for level will 'see' a negative pressure with nothing in the vessel and the LRV (lower range value) for the transmitter will be a relatively negative value, close to the (negative) span of level range.

A DP transmitter with remote seals used for level measurement will ALWAYS have a zero level reading that is a relatively large negative number because of the head pressure of the fill fluid in the capillaries.

The reason for the negative value is that the fill fluid in the high side capillary (which connects to the lower flange) pulls away from the transmitters high side diaphragm as it presses down on the lower seal by the force of gravity.

Oppositely, the fill fluid in the low side capillary (which connects to the upper flange) exerts a positive static pressure on the transmitter's low side diaphragm because the seal is up high and the fill fluid presses down on the low side transmitter diaphragm, again by the force of the acceleration of gravity.

A differential transmitter works by subtracting the low side pressure from the high side pressure:

High side minus low side = differential

As an example, in a vessel 7m tall, the transmitter has two remote seals, each 4 meters in length. The upper seal has to be above the liquid level in the head space above the liquid. The medium is water, SG = 1.00.

Assume a fill fluid with a Specific Gravity of 1.00, 4m of high side capillary and 4m of low side capillary. With nothing in the vessel (zero level), the applied pressures would be:

high side pressure = approx - 3.75m H2O (negative 3.75 meters, water column)
low side pressure = approx 3.75m H2O (positive 3.75 meters, water column)

high side minus low side = differential
-3.75m minus 3.75m = - 7.5m (negative 3.75m minus 3.75m = negative 7.5m)

The LRV (lower range value) would be approximately -7.5m H2O.

The transmitter needs to be ranged properly, with the appropriate lower range value for zero level.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How to interfacing microcontroller with a DC motor

1260


What is the use of each wire in three wire RTD

2057


Draw a great bridge circuit.

1582


What is the difference between modbus,fieldbus & profibus

1881


what is commisioning procedure,2)what is is the main work in commisioning in the field tx to dcs, plz send me detail

1866






Drum level tx with GP4 with zero elevation:7300mmh20 on HP and 8050mmh2o on LP as range but on commissioning the tx readiing is max,Why this reading?

1501


How to convert Differential pressure to flow in TPH

1762


selection of the zener barrier for the hazardeous area zone 0

1783


What is the use of double seated valve?

740


What are the different types of thermistors used in industries? How to the operation of typical thermistor?

1335


What is the Working principle of Dozing valve?

1782


what will the sending unit in the fuel gauge utilizes?

1473


Explain bernoulli’s theorem.

624


how to calibrate electro pneumatic positioner 8013 mil controls ltd ?gsr

7464


Whatis the reset ofset and control system in instrumentation

1588