capillary type tranmitter using remote seals and capillary
tubes filled with liquid of known of known density so if
you wanna callibrate it just close block valve just before
capilary @ high side & connect druck apply it's calibrated
range pressure as normal calibration ensure low side block
valve must be closed & if you asking commissioning so this
is not a DP type pressure tx so simple if you wanna put in
servie this tx just open high side block valve & than low
side block
same way i do it but still transmitter showing -13 ma.just
tell me what i want to do ?
Answer Posted / carl_ellis
A 2 wire, loop powered transmitter can not output a negative current, like -13mA. The 4-20mA output is always positive.
However, a remote seal DP transmitter used for level will 'see' a negative pressure with nothing in the vessel and the LRV (lower range value) for the transmitter will be a relatively negative value, close to the (negative) span of level range.
A DP transmitter with remote seals used for level measurement will ALWAYS have a zero level reading that is a relatively large negative number because of the head pressure of the fill fluid in the capillaries.
The reason for the negative value is that the fill fluid in the high side capillary (which connects to the lower flange) pulls away from the transmitters high side diaphragm as it presses down on the lower seal by the force of gravity.
Oppositely, the fill fluid in the low side capillary (which connects to the upper flange) exerts a positive static pressure on the transmitter's low side diaphragm because the seal is up high and the fill fluid presses down on the low side transmitter diaphragm, again by the force of the acceleration of gravity.
A differential transmitter works by subtracting the low side pressure from the high side pressure:
High side minus low side = differential
As an example, in a vessel 7m tall, the transmitter has two remote seals, each 4 meters in length. The upper seal has to be above the liquid level in the head space above the liquid. The medium is water, SG = 1.00.
Assume a fill fluid with a Specific Gravity of 1.00, 4m of high side capillary and 4m of low side capillary. With nothing in the vessel (zero level), the applied pressures would be:
high side pressure = approx - 3.75m H2O (negative 3.75 meters, water column)
low side pressure = approx 3.75m H2O (positive 3.75 meters, water column)
high side minus low side = differential
-3.75m minus 3.75m = - 7.5m (negative 3.75m minus 3.75m = negative 7.5m)
The LRV (lower range value) would be approximately -7.5m H2O.
The transmitter needs to be ranged properly, with the appropriate lower range value for zero level.
Carl Ellis
Measure First
Is This Answer Correct ? | 1 Yes | 1 No |
Post New Answer View All Answers
how the arrangement of equipments done in control room
Questions on flow meters,few questions on HART protocol,
what are the values of fuel flow rate in various places in boiler.
what are the use of belew gear in general ??
how do u calibrate the vacuum transmitter if it shows more reading
Calibration procedure for Electro magnetic Flow meter
What is 3 selection available when configure the burnout protection for controller
What is furnace draft control?
send me model hpcl questions pleas..........my mail id mohideen.dharvesh@gmail.com
What is Erosion in a control valve?
steps for installing orifice plate?
how to check earthing,what is minum ohms for proper earthing
1)How many tpes of vibration probe and how many tpyes of vibration. 2)how we can calibrate a vibration probe with tk3 3)what is RMS value in vibration measuring application and how we calculate it.
NPN transistor, SCR, Zener diode, LED, Varactor diode, Vortex meter, RTD, Resistor, Crystal
What is the use of each wire in three wire RTD