transmitter in 3 connection +,-,And test mode so how Use To Test Mode
Answer Posted / carl_ellis
The 'test' connections on a 2 wire, loop powered pressure transmitter have a diode behind them.
If a milliampmeter is connected across the test terminals (in parallel with the diode), the impedance of the meter is less than the diode's, so current will flow through the milliampmeter. There is not enough voltage drop to forward bias the diode and the diode will not conduct with a low impedance meter circuit connected across it. The diode turns off and the current flows through the meter.
Test terminals are provided for loop troubleshooting so that loop current can be measured without breaking or opening the loop circuit so that the milliampmeter can be put in series in the loop circuit.
Carl Ellis
Measure First
| Is This Answer Correct ? | 13 Yes | 0 No |
Post New Answer View All Answers
what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.
Q- What are the application in which PNP transistor is preferred over NPN ?
In which principles tx ,pressure gauge,Temp gauge,control valve works?
Question on maha cement
What is Positive Calibration and Negative Calibration?
which type of zones used for boiler? & why ?
1. what is modbus cable? 2. what kind of communication we are using for the interface of DCS, ESD and Third party cabinets? 3. What is serial communication and peer to peer communication?
List three types Level Gauges with their working principles
flow transmeter accuracy 0.075% of full scale & find ucertainty is 0.025 % so what is maximum limit band of uncertainty
Full form of KKS when use DCS.
how to turbine speed measurement?
what is the procedure for auto tune in masoneialn 12300 series displacer type transmitter?
which type inter lock use in petrochemical refinery,and oil & gas?
Explain signal isolator
With N nodes and B branches what will have a network ???