Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Essential condition for parallel operation of two single
phase transformer is that they should have same
A polarity B kVA rating
C voltage ratio D % impedance

Answer Posted / cyril

A, C and D.

Polarities of the two transformers must be the same. Otherwise, emf inducted in the 2 secondaries in parallel will cause a flow of circulating current through them, even without a connected load.
Voltage ratios must be the same. Otherwise, there will also be a flow of circulating current in the 2 secondaries if there is a voltage ratio difference.
Percentage impedance must be the same since load sharing of the transformers in parallel depends on the percentage impedance of the transformers.

Is This Answer Correct ?    11 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are dcs and plc?

1151


Is electro plating what type of load whether resistive, inductive or capacitive loads

3364


HOW TO CALCULATE ELECTRICAL, MECHANICAL,& OVERALL EFICIENCY OF GAS ENGINE POWER PLANT

2047


Draw the circuit of clapp oscillator?

1182


errection check list for transformer maintenance

2647


if a 3phase 100kva distribution transformer , 400 v,50 hz, 4-wire system is loaded at 160 k.w mostly 1-phase Lighting & Airconditioning split a.c load what will be the net effect on the power system in terms of voltage, powerfactor, current , efficiency of xformer

1941


what is the difference between droop mode and ischnorous mode in thermal powerplant?

2705


what are the Alarm, Trip & Safety equipment (Issues) present in Power Transformers pls Mail it to ashokbabunhce@gmail.com

1967


electrical

2341


how is the cable tray designed & how its total length is calculated for an Industrial plant Say for Ex. (500KW Motor Load)

1940


how desiel generate sart fail of eb?

2247


In EDO ACBs what is a purpose of closing coil and motor, what is the operation of these devices are they inetconnected. means if we give supply to motor and by BCS we charge Closing coil,what exact is operation is and how it charge a spring of ACB. Sir if anybody has an wiring diagram please send me the link to operate and EDO breaker.

2205


what is (+) and (-) in generator field detector stand for?

1887


234 MVA Generator 3 phase Short circuit current Values required? Gen set Rating-234 MVA, Gen Voltage-18kv, PF;0.8, Xdv:23.5 %, Transformer Rating-18/380KV, 680MVA,Yndd1 two winding, Step up TR, ZT:35.50 %,X/R 4.33 Gen CB Position, CB open ,Disconnected open, Generator Running Voltage 18 Kv, Bi mistakes generator side earth switch Closed during that time short circuit current level in 3 Phase required, and how to test on site 234MVA Generator Short circuit current,

2088


What is difference between SMC supportg and Glass Fibre Reinforced Plastic Support.

2390