Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

Essential condition for parallel operation of two single
phase transformer is that they should have same
A polarity B kVA rating
C voltage ratio D % impedance

Answer Posted / cyril

A, C and D.

Polarities of the two transformers must be the same. Otherwise, emf inducted in the 2 secondaries in parallel will cause a flow of circulating current through them, even without a connected load.
Voltage ratios must be the same. Otherwise, there will also be a flow of circulating current in the 2 secondaries if there is a voltage ratio difference.
Percentage impedance must be the same since load sharing of the transformers in parallel depends on the percentage impedance of the transformers.

Is This Answer Correct ?    11 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the relationship between phase & neutral

2535


what is the min and max ohmic resistance for the earthing rod installed for lighting poles for street light network

3687


What does quality factor depend on in resonance?

1033


do anyone out there know where to find a compleete list on acronyms/abbreviations used in offshore electric engineering. MCB - Micro Circuit Breaker, MCCB-Mouldes Case Circuit Breaker, ELCB-Earth Lekage Circuit Breaker, ELMCB- etc.....

2022


Why it is necessary to isolate fire fighting when you are taking shutdown for lv board.

1581


what is feeder bay?

1529


HOE WE CAN IMPROOVE BY USE OF CAPACITOR

1907


Which of the following alternatives will be cheaper (1) A 100 h.p AC, 3-phase motor (2) Four motors of 25 h.p each (3) Five motors of 20 h.p each (4) 10 motors of 10 h.p each explain

2937


L.A. (Lightening Arrester) is located at a place from where transmission line enters the transmitting substation. So L.A. (Lightening Arrester) is the first equipments which has to encounter with lightening, high voltage surges and switching surges. It has to absorb energy of lightening, high voltage surges, and switching surges. L.A. (Lightening Arrester) is made up of layers of semiconductors. If these layers can not tolerate energy released by lightening, high voltage surges, and switching surges the L.A. (Lightening Arrester) blasts.

1038


what is the power rating of CPU, CRT type moniter, LCD type moniter,scanner Approx.

2132


Define availability (operational)?

1100


Explain about retrofitting of machine tool.

1848


What is the general system requirement of alternator?

1799


circuit diagram of trip circuit supervision relay

1996


How many lightning arrestors to be installed on 50MX60MX10M building and is there any formular for that?

1925