Essential condition for parallel operation of two single
phase transformer is that they should have same
A polarity B kVA rating
C voltage ratio D % impedance
Answer Posted / cyril
A, C and D.
Polarities of the two transformers must be the same. Otherwise, emf inducted in the 2 secondaries in parallel will cause a flow of circulating current through them, even without a connected load.
Voltage ratios must be the same. Otherwise, there will also be a flow of circulating current in the 2 secondaries if there is a voltage ratio difference.
Percentage impedance must be the same since load sharing of the transformers in parallel depends on the percentage impedance of the transformers.
| Is This Answer Correct ? | 11 Yes | 3 No |
Post New Answer View All Answers
What is the function of NER and NET?
why you don not show protection and type of isolation in key single line diagram?
what is the reason the main breaker is trip during the motor is running? (some time the breaker is not trip)
what is current check gurd relay?
how to select proper cable for ct wiring so that drop within the limit.
Draw a SLD of HT distribution EB grid up to users Transformer?
How many kw will suply from one db
what should be the ideal gauge of wire (In sq mm) for different loads in Ampere?
why ups rating in kva? and why ups are in parellel?.why isolation transformer is used in ups?
Which is the oldest hydropower plant in india?
how calculate gd2 of ht motors
how to calculate maximum current
what is the difference between Power and Distribution transformers ?
what is meant by re-rolling motor? how it differs from standard motor?
. What is Electrical Life & Mechanical Life of Circuit Breaker? 2. What is Electrial Life & Mechanical Life of Magnetic Contactor? 3. What is RCD, RCCB & RCBO? 4. What is the Between defferance of RCD, RCCB & RCBO?