what are the difference between conventional and smart transmitter.
Answer Posted / carl_ellis
Smart vs Conventional transmitters
Conventional
A conventional 4-20ma transmitter regulates the loop
current and provides only a process variable signal.
The zero and span adjustments are analog adjustments. n
the case of fixed range transmitters the zero and span
adjustments are limited to about plus/minus 2-3% of the
fixed zero or span values. Some conventional transmitters
have an adjustable turndown range, but calibrating a
turndown range requires a simulated process variable (an
applied calibration pressure or a simulated temperature
(RTD or thermocouple) electrical signal). Turndown is
generally limited to about 5:1 or 6:1.
Smart
A smart transmitter provides a process signal but can also
send/receive information about the instrument itself, e.g.
zero and span info, tag (instrument loop identification),
diagnostics, or even multiple process variables using a
digital protocol.
Configuration changes are done either with a keypad and
display or through a protocol like HART, which is
superimposed on the 4-20mA signal, so no additional wiring
is needed for smart communication. HART communication is
accomplished with a handheld communicator or a modem and
software.
Turndown rangeability can be as high as 100:1 (with reduced
accuracy at the low end); 15:1 or 20:1 with stated accuracy
and can be accomplished without applying an external
calibration signal, reference or supply.
Smart transmitters can communicate via a Fieldbus,
Foundation Fieldbus or Profibus.
Carl Ellis
Measure First
| Is This Answer Correct ? | 20 Yes | 4 No |
Post New Answer View All Answers
whatis range of marcury filled tempereture gague
Operational amplifiers
what is use of communication wire in multipare cable(oil and gas field), why this communication wire not used in single pair cable?
i am from instrument branch i want paper patern of mahagenco . any pevious years paper regarding my branch send me please . please.....
NSV type probe stands for
what would be the minimum flow rate that we can measure on rotameter..?
How to calibrate the flow transmitter
How oil line flow measured?eplain about instruments used and working principle?
What is heating effect?
i have steam drum height 1000mm. and i want to placed the transmitter below the tap.how i calculate.
With N nodes and B branches what will have a network ???
Why we are using DPT(Differential Pressure Transmitter) in separator instead of level trasmitter?
in mass flow meter what is drive friquancy ?
what is the working principal of pribe
how many type conductivity sensor ?