Why Two Transformers aside shoud be supperated by concreted
wall?
Answer Posted / sasi karthick a
It is fire wall, during fault condition if transformer at
fire it should not spread to other equipment/buildings.
As per IS, the thickness should be 350mm brick wall/230mm
concrete wall. Height of the wall shall be decided based on
the height of x'frm