Our Company's Contract Demand is 110 kVA. We use 12
Capacitors each of 12.5 kVAr Capacity to maintain Power
Factor of 0.99. So, what steps should we take so that our
Contract demand does not exceed 110 kVA?

Answer Posted / 7anoter4

In order to know how much capacity to use one has to know
what is the now the actual power factor. Let’s say the
actual power factor is 0.8.Then the reactive power is
110*sqrt(1-0.8^2)=66 kVAr.
If the power factor is 0.99 then the reactive power from
the Utility will be 110*sqrt(1-0.99^2)=15.5 kVAr.
You have to compensate the difference 66-15.5=50.5 kVAr so
4*12.5=50 kVAr it is enough.

Is This Answer Correct ?    7 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to calculate slip ring induction motor stator and rotor currents??

1745


what is meant by poly phase induction motor ? how its operating by single phase or three phase?

1737


working principle of AC Servo Motor with its construction

8345


We are preparing another project which involves Waste heat recovery from a 1 MW GE Engine. The Engine in particular gives out flue gas at 487Deg C with a flow rate of 5650 kg/hour and this can be cooled to 180 Deg C. This gives a thermal output of ~ 594 KW that is available for input to VAM via heat exchanger / boiler. Additionally 581 KW will be available from engine jacket water (temperature profile 80/ 80 Deg C and a flow rate of 50m3/hr) Our estimation is that 300 TR of cooling is possible with a suitable VAM machine(s). Please advise what is the most suitable arrangement with maximum TR and min Capital expenditure. plz reply me as early as possible

1504


PLZ EXPLAIN CORONA,SKIN,BIRD PALE,SPAN,SAG Effects of power cable.

1537






What Normal(Tangent) towers and Tension(Cut-point) Towers?

5234


Rules and standards of electrical control wiring ?

646


How to Preparation of online test

1082


What are approaches to tackle sedimentation problem of reservoir?

596


what is RFID? thire application;

1539


Vibromotor 252MV 1/4HP2P..what is mean by 252MV?

1537


What is safety of Ht panel

1186


can i connect wavetrap in 2 different phase in EHV line?

1373


difrent between vcb acb sf6 and mccb breakers

4626


What do you mean by per capita requirement of electrical energy in india

1662