Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

If the kvar rating of capacitor bank is
600 kvar at 525V then what it's rating at
415v.

Answer Posted / ahamadkutty

THE MAXIMUM CURRENT RATING OF THE 600kVAR CAPCITOR IS
600000/525/1.7321= 660 AMPS.SO AT 415 VOLTS LIMITING THE
CURRENT TO 660 AMPS THE RATING WOULD BE 415x660*1.7321=
474.3kVAR

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the function of choke in the flourcent tube lights and why the colour is in white mostly in flourcent tube lights

1890


what is the method of earthing of a transformer using electrodes?

2199


how to check ac servo motor

2192


why should the primary of transformer be connected in delta in a heat run test?

1918


Is there any question in the name of Static Switch in UPS??

1905


is it possible to have dc motors on single chip

1773


A 10 MVA, 66KV, 50Hz, Y-connected 3-phase alternator has synchronous reactance of 0.635 Ù. It is working at full load at 0.8 lagging p.f. condition. Find torque angle, neglect armature resistance.

2534


describe the A.C. Generator Testing procedure

2111


advantage and disadvantage of team work?

1642


Name a govt approved university which have 100% online engineering course.

1661


what is doubling factor in making current of a breaker?

2007


a)In a 3-phase 4-wire circuit, a circuit breaker is selected to protect the circuit whose highest fault level is 6.6 MVA. Determine the required minimum breaking capacity in kA. (Note: Covert 3-phase power in terms of kA to find answer.) b)Using the below, determine the required minimum making capacity in kA as a “peak value”. Rate breaking capacity (Icn) ka: Icn<= 1.5 Factor = 1.41 1.5

1648


how calculate the electrical load for industry and office

9201


define digital electronic

1934


How to calculate the input cable rating for 10kva ups (3phase input and single phase output and also 3phase output, battery rating 65Ah)provide the formula also.thnx

2153