why we are using negative range like -750 to 0 mmwc in
closed tank?and what is the reason can you explain clear?
Answer Posted / varma
In Closed tanks vapour condensates and accumulate in LP impulse line, to eliminate this problem glycol will be filled
in LP impulse line. The positive head pressure which is created by the glycol density and the height of the LP impulse line has to be suppressed. For example LRV and URV are 0 to 750mmh2o, 750mmh20 of positive head pressure to be substrated for each value then u will get the value of LRV and URV as -750 to 0mmh2o.
| Is This Answer Correct ? | 4 Yes | 2 No |
Post New Answer View All Answers
I need control valve ISA hand book. Is there any site to download that big book containing all the pages. Written by Paul Friedmann
List three types Level Gauges with their working principles
Explain why plc require in analog input 4-20amp & 0-10 volt?
How to convert Differential pressure to flow in TPH
draw the block diagram of a level transmitter ?
How do bending tubing provide better measurement than using tubing fittings such as elbows?
Can combine control system for Emergency control system (ESD)and Fire & Gas System ( F & G) is possble to built and offer to client? Can such system is as per Norms in India?
What is the minimum rating availalbe for weld neck orifice in market?
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?
how to measure oxygen which methods are using?
Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?
hello can yoy pls send me previous papers of jindalpower and steel ltd.....'m from instrumentation..... mani1048@gmail.com
what is performance test.need defination
use of split range ? where it is used ? in which control loop it is used ?
When doing a liquid seal on a differential flow transmitter , most of the time the sealing liquid will be heavier then the process fluid. For wich application will the sealing liquid be lighter than the process fluid if transmitter is mounted below the process line.