If a control valve is hunting means means if we are giving
50% to the cv, the cv will open at 51% then slowly slwoly
it will reaches 49% , then it will reaches again 50%, this
type of action occured frequntly.. so what to do for solve
this problem. The possible cause is in volume booster or
positioner's relay.. positioner is double acting .. and
make siemens..sipart.The cv is double acting and mounted
for anti surge operation, it having 4 nos. volume booster,
one sov, one positioner, etc..?
Answer Posted / avinash d. pagar
Also please check volume booster function separately with
out positioner and then set factory setting of positioner.
again calibrate positioner by auto calibration. mostly
hunting and over shooting issues cause by booster error.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
Why do we have earthing cable in branch cable and shield in the same cable?
How can we use feedback signal frm rtd for monitoring and in dcs for controlling ,then which type of rtd is sutaible 2 , 3,4wire and why ?
How to convert Differential pressure to flow in TPH
how can be calibrate flow indication transmitter (rosemount) it shows excess milli amps nearly about 24 ma on full scale, but its scale was set on 20ma on full scale..???how can be simiulate..???
What is the basic difference between Modbus and CAN Open Protocols
key phaser where is use and work
List three types Level Gauges with their working principles
How to calibration a control valve?
Operational amplifiers
what is a vortex flow meter,mass flow meter and electromagnetic flow meter.particular use of this.means in which condition particular meter is used.
WHAT IS THE DIFF. BETWEEN SKIN TEMPERATURE AND PASSES TEMPERATURE..?
Explain why plc require in analog input 4-20amp & 0-10 volt?
What is first echo & echo window in radar type level transmitter?
components of control circuit belongs to control valve
Can u tell me the principle of the tc,rtd,level switch,pressure switch ,transmitter(pr flow level temp.),vibration...plz