In a 3 phase,400v,4 wire system, 2 incandescent lamps, one
having 230v,100w and the other 230v,200w are connected between
r phase- neutral and y phase-neutral respectively. If neutral
wire breaks which lamp will fuse first and why?
Answer Posted / velmurugan
100W lamp will fail first, Although the voltage across 100 w
lamp will be higher (293V), but it will fail because of
effective current (0.489A) which is more than the 100 w
lamp normal current (0.4A). Increase in current cause more
heat and heating element will fail.
Is This Answer Correct ? | 6 Yes | 3 No |
Post New Answer View All Answers
If Neutral Grounding Resistor (GR) failed/shorted. Is it repairable.
How to calculate phase to phase difference ?
Briefly describe your ideal job?
If you don’t have coal, salt and copper, then how would you earth your connection temporarily at a camp site.?
Can i replace Earth leakage relay to the faulty Earth Faulty Relay
Can we use BS 6651 and BS EN 62305 standards for computer room lightning ptotection in substation?
Why r u using pf panel. what the uses
can we conduct the swineburne's test on a dc series motor? why?
what is per unit calculation?looking for simple and strong explanation thk u
how to calculate the breaking capacity of different breakers.
hello friends..... any one have papers or any study materials?sail ,hpcl...?
What is the ratio of Booster transformer?
Can you used moeller lzm1 mccb in a dc system with 125vdc and 20ka short circuit current , beside is it have 24 or 48 volt shunt ? Beside how long current can through from An MCB shunt contacts? (like Z7-AS 24 V)?
can we make a electric generator,which can not use any type of fuel,air,solar,gas,thermal,coal,petrol,etc and able to produce electrical energy (or self electricity generating generator)
why we can stote dc? why we cant store ac?