In a 3 phase,400v,4 wire system, 2 incandescent lamps, one
having 230v,100w and the other 230v,200w are connected between
r phase- neutral and y phase-neutral respectively. If neutral
wire breaks which lamp will fuse first and why?
Answer Posted / velmurugan
100W lamp will fail first, Although the voltage across 100 w
lamp will be higher (293V), but it will fail because of
effective current (0.489A) which is more than the 100 w
lamp normal current (0.4A). Increase in current cause more
heat and heating element will fail.
| Is This Answer Correct ? | 6 Yes | 3 No |
Post New Answer View All Answers
what clearance required for 4.5 mva dry type transformer?
all interview questions with answers of ntpc (2000-2009
what's the difference between 'shaft power demand' and 'BHP' , when we consider electrical load list.
how to calculate regulation constants for over head lines? and what are the regulation constant for raccoon conductor at different voltage level and different P.F?
he compression ratio for a petrol engine generally lies between
How to Prepare preventive maintenance shedule of machine tool.
How can ou verify the size of conductor 50Sq.mm ACSR
What is given by the definition in BIL IMP/PF = 950/395 kV. This was found in a name plate of a power transformer.
What are the basic elements used for modeling mechanical rotational system?
in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?
A generating system will have a total capacity of 300 MW. Find the probable forced outage when the capacity is supplied by two 150 MW units. The operating probability of all units is P=0.98 and forced outage probability rate Q =0.02 .
what is the disadvantages of common earthing for AC and DC equipment? (i am talking about inverter control room and inverter duty transformer earthing is common...?)
What is mean 2XWY
Please help me regarding my one concern. - During earth pit testing we noticed that the Clean earth pit and dirty earth pit showing continuity (Resistance value - 5ohm) . I want to know that if both earth pit have separate location and there is not internal looping between PIT then why such continuity is showing on it . Because of this issue the field side all earthing point showing short. In PLC panel we are providing two types of earthing cable which is coming from separate earth pit (Clean and Dirty earth pit) because of earth PIT showing short our PLC is not complying spec . please help regarding this issues.
Where can i get practical knowledge of solar system?