In a 3 phase,400v,4 wire system, 2 incandescent lamps, one
having 230v,100w and the other 230v,200w are connected between
r phase- neutral and y phase-neutral respectively. If neutral
wire breaks which lamp will fuse first and why?
Answer Posted / velmurugan
100W lamp will fail first, Although the voltage across 100 w
lamp will be higher (293V), but it will fail because of
effective current (0.489A) which is more than the 100 w
lamp normal current (0.4A). Increase in current cause more
heat and heating element will fail.
| Is This Answer Correct ? | 6 Yes | 3 No |
Post New Answer View All Answers
What is the Diff. btw Manule Pull Station & Manule Abort Station Switches used in FM200 System??
How is the resonant peak, resonant frequency, and bandwidth determined from nichols chart?
Why is the frequency not changed during transformation of electrical energy in a transformer?
what size steel armoured cable is required to support 1500kva capacity. would 70mm squared be enough or would I need 90 or 120mm squared 3c plus earth
Either the Armoured Earthing strip of HT 3 core cable have to pass through CB CT or not , why ???
Pl.brief me any electrical major fault you have rectified.
iam using DM 3251 voltmeter(1 percent accuracy)for 11KV system PT ratio is 11KV/110V.can anybody explain what is the max and min voltage deviation.
acb(AIR CIRCUIT BREAKER)NOT CHARGING AUTO
What is a compensator?
Why slip ring ind. motor power consumption is low compare to induction motor .same 90 kw motor used same load output
What is kirchoff ’s current law (kcl)?
1. If 8.35%Z means the percentage impedance of 132kV-line from power company, we will like to confirm its base capacity?
What is the function of a neutral reactor.
What Should be the value of Vector Surge angle at Tripping and how to calculate it?
What is the rate of WCT on the Electrical Contracts comprising of DG Sets and Civil Works in Delhi ?