Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I saw one P&ID 6" control valve has been connected with 8"
process line, and 2" valve also connected in parallel with
6" valve. why the 2" valve connected in parallel, Is there
any technical reason. please clarify. With Regards-Kittu

Answer Posted / girishkumar

It is called split range control and split a big CV into two
parts as 1:4 for fine control.ie:- in 0% both valves keep in
close. In 25% the 2" valve keeps fully open and 6" keeps
fully close. In 50% the 2" keeps fully open and 6"keeps in
25%open. In 75% the 2" keeps fully open and 6"keep 50% open
and in 100% both keeps fully open.These two valves
controlled by same controller with two AO.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Basically iam Instruemntation Engineer, but Iam interested in Instruments design engineering, so plz guide, is there any course, training or Softwres to become Instrument design engineer??.

2050


what is use of communication wire in multipare cable(oil and gas field), why this communication wire not used in single pair cable?

2169


why we use the ac supply load cell>?can we use the dc supply load cell?advantages and disadvantage of the ac supply load cell?

6412


Which products are available in the Mass Systemswitch and System Manager AC range?

1879


I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration  So is there any causes biside this or  any  permissives ?

1853


in mass flow meter what is drive friquancy ?

2095


How to Calibrate Interface Level Troll in field

1366


Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .

1708


what is cems analyzer explain with principle and drawing ?

2383


Why do we floating DC in DC system.

2898


Im having problems with interfase betwen SPI v7.0 and SPPID v5.05. Previous versions of Intools shoul be fixed with SPPIDproj.ocx file. It was necessary to replace this file with one that allows the connection between different versions of SPPID. It is necessary in the current version to do the same?Thanks

2309


give me all the details about the interview and which type of question being asked

2226


how can be calibrate flow indication transmitter (rosemount) it shows excess milli amps nearly about 24 ma on full scale, but its scale was set on 20ma on full scale..???how can be simiulate..???

2406


what is the electrical operation procedure for switching on 27.6MVA electric furnace.

2031


how will you check torque value during Factory acceptance Test for control valve/ESD ON/OFF VALE how will you confirm this torque value is being correct, Which document will you be refer.

2488