In a 3 phase,400v,4 wire system, 2 incandescent lamps, one
having 230v,100w and the other 230v,200w are connected between
r phase- neutral and y phase-neutral respectively. If neutral
wire breaks which lamp will fuse first and why?
Answer Posted / awdhesh
When neutral disconeted bulb are in series so ckt current is same but voltage drop is diffrent.vlt drop is propesanl to R so 100W lamp R is more with respect to 200W. 100 W lamp fuse first.
| Is This Answer Correct ? | 36 Yes | 5 No |
Post New Answer View All Answers
How can we calculate the efficiency of a Running (On-Load) Motor ? What parameters are required and what is the method ?
How may I get the maximum current capacity for a particullar size Alluminum or Copper cable if there is compulsion to use?
How the over load setting for HT Motors calculated-provided in Numerical Relay
How colour picturetube works & how many year it will works.
mccb service sittings be done?
How wire size can define in electrical wiring? What is the ratio?
We have a distribution transformer of 750KVA/11kv/440v and an AVR (Servo Stabilizer) of 750KVA on the LT side of distribution transformer. Also we have an ACB of 1200A on the output of distribution transformer (that is on the input of AVR). We want to have an MCCB on the output of AVR. What should be the rating?
Iin ESP why positive is grounded ? why not negative ?
How eddy current generation support the idea of train braking?
DG cranking voltage?
Can any body tell gulf interview question for experienced electrical engineer ?
What is the normal phase difference between the voltage and the no-load current in a transformer?
can we choose current transformer secondary, to calculate residual flux in a power transformer, so as its saturation is close to the saturation level of power transformer?
What is the resonant peak?
WHAT ARE THE DATAS REQUIRED FOR PROTECTION AND METERING AND CONTROL AND LOGIC PREPARATION,HOW TO STUDY THE PROTECTION AND METERING?