What are the problems faced while testing HART instruments?
Answer Posted / carl_ellis
Failure to connect with HART can be a laundry list of
issues, the most common of which is the
lack of minimum 230 ohm resistance in the loop.
Other reasons can be
- HART probes connected across the DC power supply, not in
the loop
- failed DC power supply
- electrically noisy DC power supply
- HART modem lacks installed PC driver or internal setup
(serial modems were touchy)
- HART device not at expected HART address (address zero for
point-to-point comm)
- device does not have HART option or HART option has been
disabled.
- HART option replaced by different fieldbus comm card (it's
happened! !)
- Connecting across the test terminals on a pressure
transmitter where there's no HART signal
- HART communicator is dysfunctional or its batteries are
discharged
- lack of DD in communicator/program limits access to the
common commands
Carl Ellis
Measure First
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Please any one can provide latest aptitude test,technical test and interview questions for tata consulting engineering (TCE) i need it asap thanks in advance
WHY THE DEGREE OF VALVE PLUG AND VALVE SEAT IS SLIGTLY DIFFERENT I CONTROL VALVE TRIM DESIGN
What is difference between ESD and PLC please Explain me clearly.
I m appointed as an automation trainee engineer in small firm in that I am only the one , my company give me a project on s7-200 as i m beginner I don't know how to program so please send me the helpful site so that I complete my project before deadline....please help me out in this critical situation.
how u calibrate pneumatic n motorized c/v?
Why rdt and thermocouple both give different output .and one things more, how to generate ohm or mili volt plz mail me merajalam143545@yahoo.com
How works weighfeeders in cement industry? what is the working principle?
How to calibrate radar type level transmitter for interface level? Total liquid(liq.1 and liq.2), level both the liq individually? For. Both the liquid levels how the signal will go from transmitter to dcs? How to calibrate. Single radar 9:26:55 AM for 2 different liquids in a tank?
Name different types of bourdon tubes.
How is automatic reference junction compensation carried out in temperature recorders?
I faced several time siemens ps2 positioner automatically getting Chang in it's set point direction after auto calibration So is there any causes biside this or any permissives ?
what is the process for double acting cylinder pneumatic for 32' v/v
Instrumentation symbols interpration, P& ID, Logic diagram analysis, Electrical drawing analysis.
line up procedure for dp type flow transmitter?
What is Span Error