Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

What is 100%
protection of
generator? Why
95% protection
is used not 100%?

Answer Posted / aswin joseph

95% stator earth fault protection uses an overvoltage relay at the neutral transformer of a generator. Because there is always a minimum voltage at the neutral because of harmonics and zero sequence, a little margin is necessary and only 95% of the generator windings can be covered with this method.
100% stator earth fault protection uses current injection at low frequency or minimum third harmonic voltage to detect earth faults. It does not have the limitation at the earth side of the winding, so using this method and the one described for the 95% you can cover 100% of the stator.
Both detect earth faults at generator stator windings when generators neutrals are connected to earth using neutral transformers or reactance, which make neutral currents too small to use overcurrent relays.
Injection method protects 100% stator windings without the need of a 95% relay. It works on its own.
The principle is the following: a signal generator injects voltage pulses in the windings of the machine at a frequency different from the rate frequency of the system or any harmonic (typically 10 Hz to 25 Hz, 87 Hz...). These pulses are transmitted to ground through the winding insulation and back to the signal generator through the earthing resistor.
Together with the signal generator, the relay also measures the current in the signal injected. In normal conditions, total impedance is high and low currents are measured. If there is a phase to earth fault in any phase, impedance to ground decreases and current increases rapidly, indicating the fault.
This method works even with the machine out of service if the relay is connected (careful with this during maintenance).
This system is normally implemented at the generator neutral transformer, but if it is not available (for example, because a resistance or reactance is used instead of a transformer, or the generator is delta connected), voltage transformers can be connected at the generator terminals with the secondary connected in broken delta, since this allows the injection of the same signal to all windings.

Is This Answer Correct ?    32 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

A well system is when , no. of bus bar is less or more. Tell me the concept of it.

1916


From what on-site components does the HT panel monitoring the bus-bars in a 11kV system take inputs?

2003


what is the minimum winding resistance of 30hp compressor, to run or to switch on

1867


hi I have done 3 yrs diploma in electrical engg after 10+2. I have 16 years of work experience into design proposals sales and engg application development in LV/MV swithcgear and sub station automation field. I want to apply for immigration to new zealand but I am not sure whether I qualify or not since I dont have a degree. Can anyone advice? Thanks Riz

2271


what parameters are should nessary for control technic dc drive(in rolling mills)?

1974


8. A DYNAMOMETER TYPE WATTMETER RESPONDS TO THE.......

9275


Write the analogous electrical elements in force current analogy for the elements of mechanical translational system.

1253


What information we need to prepare relay coordination chart

2326


can we install HT panel & LT panel side by side or how much clearance is required ?

1588


i am completed my degree(B.E EEE) 2014 anychance to get electrical licence plz help me

2143


Generation of voltage for each phase are same of a turbogenerator.Although the short circuit current flow when two phase of turbogenerator are shorted(where current can't flow without potential difference),why?

2114


what are inherent currents?

2014


WHAT IS DOL STARTER? HOW IT WORK? GIVE ITS CONTROL AND POWER DIAGRAM .

2169


For some transformers we are using solid neutral earthing while some others we are using resistance earthing why ?

1893


How to test the vector group of a Yd11 transformer? what are the relations to be checked between various vectors to confirm this vector group?

4466