How can we check Zero of DP type Level Transmitter onside?
Answer Posted / muhammad yasir
close HP isolation valve open HP side drain valve.Transimiter read maximum Differential pressure and Transimiter show O% Level or 4ma because LP lmpluse line liqued act pressure on LP side Transimiter.
When span check close both HP and LP side valves and open drain valve Transimiter read 0 differential pressure.Transimitter show 100% level or 20ma.
| Is This Answer Correct ? | 1 Yes | 2 No |
Post New Answer View All Answers
sir,would you please send me the Hindustan petroleum corporation limited papers(HPCL).my e-mail ID is ujjwal_sharma1983@yahoo.com
Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell
Dear Friends, we are planning to design Power distribution and Fiber optic in the same cabinet.Like Front side Fiber optic and Rear side Power distribution.Is it any possibility of problem occurs like interference etc? Your answer is highly appreciate.
how to control pid
IS there any effect of vortex in low pressure side of the transmiter after the orific in feed water line? if yes then what is the calculation?
why we are using digital signals for I/O & how to measure this signals is getting or not ?
Explain the use of hair spring in the pressure gauge.
Please can anybody help for control valve sizing step by step procedure?
Drum level tx with GP4 with zero elevation:7300mmh20 on HP and 8050mmh2o on LP as range but on commissioning the tx readiing is max,Why this reading?
how to relay switch sense the fault?
How to Calibrate Interface Level Troll in field
A PLC is programmed to drive three motors A, B and C as follows : After running motor A for an hour, motor B should get ON and motor A should get OFF. And after running motor B for an hour, motor C should get ON and motor B should get OFF. And after running motor C for an hour, motor A should get ON and motor C should get OFF. (That is, a cyclic repetition with time period one hour) Now, the second condition is: If any motor gone faulty and is tripped, the consecutive motor should get ON and the faulty (tripped) motor should be eliminated from cyclic repetition. The remaining two motors should bear the cyclic repetition of one hour each. (For healthy motor take logic as high and for tripped motor take logic as low) Now, the third condition is: When motor A load(Amps) exceeds 60% of its rated load, motor B should get ON in parallel to motor A. And when both motors A & B are running in parallel, and if their load exceeds 60% of their rated load, motor C should also start in parallel to A & B. [Here the cyclic repetition is eliminated, until their loads become normal(40%)] [Take logic high(1) for load at 60% and logic low(0) for load at 40%] Now draw a flow chart or a ladder diagram to fulfill the above condition.
What is three element drum level control system why its better than single element?
What inherent design and operating principles are included in a modern control system to use predictive maintenance practices to increase overall system reliability?
how to convert MA in to measuring values..and how mwasuring values into MA ?..plz ansr.i have intervw