Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I have a LT of 10000mmwc range. can i use this LT in 1000mmwc range of tank?? if yes than what happened???

Answer Posted / carl_ellis

I have a LT of 10000mmwc range. can i use this LT in
1000mmwc range of tank?? if yes than what happened???

A change from a range of 10000 mmwc to 1000 mmwc is a turn
down of 10:1

If your transmitter supports a minimum range of 1000 mmwc
within the accuracy spec you require, then re-range the

transmitter and use it.

Most smart DP transmitters from major manufacturers will
support this.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is modbus?

1214


1. what is modbus cable? 2. what kind of communication we are using for the interface of DCS, ESD and Third party cabinets? 3. What is serial communication and peer to peer communication?

2220


is there any digitel grevity meter availaible in the market by which we can measure specific gravity of a battery?

2229


what is cems analyzer explain with principle and drawing ?

2391


What is the basic difference between Modbus and CAN Open Protocols

6457


Any body have know try work calculation ???

1438


What care will you take in the installation of control valves,SCADA,DCS and FOC in Oil and Gas Project?

2137


What are the interlocks we have to check during the start up of LP/HP compressor?

2012


Yokogawa CENTUMVP R6.09 unable to download to Engineering Station with ExaOPC R3.75 The issue is when I try to download the common project section to the Engineering Station (STN) from the HIS in System View, it is unable to connect. The error displayed is: WARNING: Could not connect to equalize destination. (7001) Retrying. Number of retries = 0/1 ERROR: LdXopsLoadMain: connect error 10060 ERROR: Processing terminated due to connection error. (7002) Equalization end with errors. STN0149 ---- ERROR = 2 WARNING = 1 ---- Background: >Updated the ExaOPC software on the STN from 3.60 to 3.75 >STN operating system is Windows Server 2008 R2 >HIS operating system is Windows Server 2016 Stanard Solutions attempted include: >Ensuring all IP addresses are correct and all networked devices can be pinged. >The ability to ping a device using its host name from another device ( from HIS) >Ensure both devices firewalls are disabled. >The antivirus installed on the STN is disabled. >Ensuring both devices are within the same workgroup. >Added both devices to each other's Host and LMHost files. >Running IT Security tool after changing any administrative settings.

2198


How d.p. Transmitter can be applied to open tank?

1140


Which type of pressure can be measured by primary elements?

1053


How the sizing of the analog signal cable is calculate?

2534


how to calibrate load cell

2846


What is the constant voltage unit?

1091


HOW TO SOLVE PROBLEM WITH ENRAF LEVEL TRANSMITTER 854 ATG THAT PASSWARD DO NOT Exist INTO TRANSMITTER TO ADJUST LEVEL WITH PORTABLE PET 847, WRITTEN WRONG PASSWORD , I AM SURE THAT DEFAULT PASSWARD (W2=ENRAF2) IS THIS TRANSMITTER NEED TO REPLACE SOFTWARE AND HOW?

3527