Dear all... I have 1 0-400 duplex type RTD, I connected the
A side to the temperature indicator and B side to the PLC
panel, but when I have observed then found that The PLC side
temp has the variation. and it was distub to other RTD temp
also. so what can I do.
Answer Posted / carl_ellis
The RTD element is ALWAYS isolated from the sheath. Dual
element RTDs should be isolated from each other.
Therefore, there should be no common electrical connection
between any wire in a dual element RTD.
The fact that a connection to one receiver (the PLC)
disturbs the other receiver's RTD reading means either
a) the RTD elements or lead wires are shorting to either
the sheath, the other RTD element or a lead wire; meaning
the RTD assembly is damaged internally.
b) the field wiring for one RTD is shorting to the field
wiring of the other RTD
Carl Ellis
Measure First
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How many interlocks at turbine side?
when placing a vent or drain hole on an orifice plate should you measure from the center of the bore up or down for the vent placement?
What is megering????
How will you calibrate PID controller? explain with example.
What is the use of temprature compensation?
HOW TO CALCULATE ACCURACY OF AN INSTRUMENT. WHICH IS COMPITABLE FOR USE.
Define the difference between a stable versus an unstable controlled system and some of the tools you might use to be able to detect when this is happening and assumptions used for control system application design that could contribute to instability
If relative y axis vibration sensor is by passed, and relative x axis and absolute sensor is left working. how much monitoring i would have risked?
diff between neutral ,ground,phase , earthing and shielding?
I want to know the questions asked in ONGC interview(after being selected in the written exam) for Instrumentation branch.Kindly help.
which type of filter gives the constant phase characteristics?
hello friends, can you please send me the model paper or question paper to be prepared for hpcl examinations????????? You can mail me at rahim_here@yahoo.com waiting for your reply........... help me .. plz.....
Why do we have earthing cable in branch cable and shield in the same cable?
1.what is controller proportional gain 2.what is the controller intergral action time. 3.A proportional plus derivative controller that has a proportional band of 20% and a derivative action time of 0.1 minutes. Construct the shape of the output waveform for the triangular input if the input rises and falls at the rate of 4 units per minute.
what is the advantage of submersible level transmitter compare to ultrasonic level transmitter?