how to set calibration range in a DP transmitter to measure
level for a closed tank and for an open tank,and also please
explain me how to set calibration range for a DP flow
transmitter in a line ?
Answer Posted / carl_ellis
Configuring the range for a DP transmitter
Open tank:
- Flanged DP transmitter
- high side at lower flange
- no remote seals:
- units: water column units = uwc
- LRV = 0.00 uwc
- URV = physical upper level elevation (uwc) * specific
gravity of fluid
Closed tank:
- flanged DP transmitter
- high side at lower flange
- no remote seals
- dry leg from vapor space above liquid is piped/connected
to the low side
- LRV = 0.00 uwc
- URV = physical upper level elevation (uwc) * specific
gravity of fluid
When the receiver (DCS/PLC/indicator/recorder) receives the
level signal, it converts to physical level elevation by
dividing the process level signal by the specific gravity
and scaling to physical level units.
Volumetric flow rate with DP transmitter on DP flow element:
- units: water column units = uwc
- LRV = 0.00
- URV = maximum DP value at the maximum flow rate stated
on the sizing sheet of the DP flow element
Whether the signal is square rooted in the transmitter or
in the receiver for conversion to flow rate is up to the
plant convention/standards.
| Is This Answer Correct ? | 2 Yes | 5 No |
Post New Answer View All Answers
How many ohms are required for proper earthing?
Make Heater Process Logic.
How the sizing of the analog signal cable is calculate?
Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure
Specify ideal accuracy of flow element like orifice plate, Ventury, Annubar. Ultrasonic flow meter etc.
Explain the combusion chamber
centrifugal compressor interlock? Tell me the parameter at which compressor will trip
Why MUX JB's are using only Temperature Element in Fundation field bus?
What is the GK Value in Flowmeter?
find the kp ki kd from the transper function G(S)=29.44s+04707/1.5349s2+s
plz tell me clearly about PID.."when v have to change I value,D value,GAIN??
what is intrinscily safe system and where we use?
what is your eligibility criteria for freashers?
can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.
sir ,iam in dem urgent need of HPCL Paper of Instrumentation Branch plz send me at your earliest convenience at ujjwal_sharma1983@yahoo.com