i want the equation of this question.
Tranmitter range is 120 mmwc and dcs flow range is 1700 nm3/hr. if i want to change dcs range from 1700 to 2400 nm3/hr then how much dp i have to enter in transmitter
Answer Posted / carl_ellis
Answer: 239.2 mmH2O
Present max flow rate = 1700 nm3/hr
Present max DP (at max flow rate) = 120 mm H2O
New max flow rate = 2400 nm3/hr
New max DP (at new max flow rate) = x
2400/1700 = 1.412 or an increase of 141.2% in flow rate.
The DP and the flow rate relationship is a square root relationship, but the calculation is based on normalized percentage.
X = 1.412^2*120
X = 1.993*120
X = 239.2 mmH2O
The increase in max DP from 120 to 239.2 mmH2O is an increase of
239.2/120 = 1.993 or 199.3% increase in max DP at max flow rate.
Sq root of 1.993 = 1.412 or 141.2% increase in max flow rate (2400/1700)
Carl Ellis
Measure First
| Is This Answer Correct ? | 13 Yes | 0 No |
Post New Answer View All Answers
How the sizing of the analog signal cable is calculate?
what would be the minimum flow rate that we can measure on rotameter..?
please any body have most important data for study for saudi aramco test of instrument QC thanks email shahnaveedullah@gmail.com
full process of gas turbin?
how pressure transmitter work, what is its principal to measure and how its generate signal. for pressure transmitterinstallation which precautions must be taken ??
What is eddy current? Describe the operating principle of proximity probe.
Why all the drains(Gland sealing,ESV,Casing inlet etc) are directly connected to the flash tank instead of hotwell of the condensor in the power plant? My Email Id:naba02222@gmail.com
what is the vital subject for scoring bhel exam&what is the question pattern
hiii.... can any one provide me previous years question paper of hindustan petroleum for instrumentation engineering???
HOW TO CALCULATE ACCURACY OF AN INSTRUMENT. WHICH IS COMPITABLE FOR USE.
Please send me the sample question of Instrumentation of hpcl/iocl exam. my mail id hihi_kiholo@rediffmail.com
can we copy the software from a transmitter using hht(hart 275) ?
in mass flow meter what is drive friquancy ?
how many types of viberation transmitter and how to calibrate and where use of vibration transmitter
Where are oxygen analysers installed in cfbc boilers? What are their usual readings?