Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

10Hp, 3-phase, 415v, 50Hz induction motor.
The above motor is to run on Star-Delta connection, so how
do i make following hardware selection
1) MCB, 2) Contactor, 3) Wire Gage (Depending on P-P current
or Line Current), 4) OLR,
Please tell in detail how to do the above, so as to get the
ans. of it even if the Hp rating changes.

Answer Posted / 7anoter4

10 hp=7.5 kW. The manufacturer has to indicate the starting
current.
Let's say the motor is designed for star/delta starting
then according to IEC 60034-12 Tab2 for 6.3 kw up to 25 kw
S1=12 then maximum permissible starting current will be
Istart=12*7.5*1000/1.73/415=125.2 A.
The short-circuit protection has to be set at
1.25*125.2=156.5 A.
The circuit breaker rating has to be 150 A. The motor
overload has to be set at 1.25*Irated and also will trip
the breaker if the current of 2*Irated will last more than
the permissible stall time [let’s say 4 sec].
The supply cable allowable current [see IEC 60364-5-52]
shall be 1.25*Irated.
Usually a 7.5 kW motor at 415 V rated current will be 13-16
A then the cable permissible minimum should be 20 A.
According to the above mentioned standard 2.5 mm^2 copper
conductor PVC insulated will be ok.
You have to check the voltage drop also: no more than 3%
rated and 10% at start. If DV=1.73*I*[R*cos(fi)+X*sin
(fi)].R,X =total resistance-at 70 dgr.C- and reactance
[ohm].
cos(fi)=0.85 [approx.] rated and 0.3 at start. Sin(fi)=
(1-cos(fi)^2)^0.5.
In this case if the cable length will be 80 m 4 mm^2 copper
conductor has to be employed.

Is This Answer Correct ?    6 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the function of a neutral reactor.

1927


I WANT TO know WHICH WAY IS BETTER FOR CONNECTION BETWEEN POWER TRANSFORMER AND MAIN DISTRIBUTION PANEL. 1-IS BETTER WE USE CABLE? 2-IS BETTER WE USE BUS DUCT? my transformer rate power is 2500KVA

3304


Explain and give me an example of a time when you had to explain some new procedures to your co-workers for quality service delivery, how did you go about it?

2032


(1)Can earth and be conected together (2) what is the diferent between earth & neutral

1853


How to distinguish whether MCB is DC or AC looking at it physically

2027


explain the functions of main isolation switches

1722


how to calculate sizing of NGTR (Transformer rating,Loading resistor value and Current rating of resistor) and what is the X/R ratio. Details : 11kV,Capacitance 1.73532 micro farads,40kA for 1sec.

2324


why in an industry; machine having rated 200 h.p stopped after power factor is maintained above 0.97 lag by control panel in view-of energy saving

2248


I want formula to calculate cable size as per load given in length & amp. I searched many sites but didn't right answer. Please reply me asap.

1510


What is the basis for framing the rules of block diagram reduction technique?

1582


What is the formula for calculating the Instantaneous Short Circuit & overcurrent for any breaker

2056


What are the types of piano switches?

2075


which one is more efficient, torq, power & ecnomy with the same frame size AC motor / DC motor?

2233


Load transfer in 11kv double busbar switchgear - operation.

2009


Explain thin film resistors and wire-wound resistors

1074