10Hp, 3-phase, 415v, 50Hz induction motor.
The above motor is to run on Star-Delta connection, so how
do i make following hardware selection
1) MCB, 2) Contactor, 3) Wire Gage (Depending on P-P current
or Line Current), 4) OLR,
Please tell in detail how to do the above, so as to get the
ans. of it even if the Hp rating changes.
Answer Posted / 7anoter4
10 hp=7.5 kW. The manufacturer has to indicate the starting
current.
Let's say the motor is designed for star/delta starting
then according to IEC 60034-12 Tab2 for 6.3 kw up to 25 kw
S1=12 then maximum permissible starting current will be
Istart=12*7.5*1000/1.73/415=125.2 A.
The short-circuit protection has to be set at
1.25*125.2=156.5 A.
The circuit breaker rating has to be 150 A. The motor
overload has to be set at 1.25*Irated and also will trip
the breaker if the current of 2*Irated will last more than
the permissible stall time [let’s say 4 sec].
The supply cable allowable current [see IEC 60364-5-52]
shall be 1.25*Irated.
Usually a 7.5 kW motor at 415 V rated current will be 13-16
A then the cable permissible minimum should be 20 A.
According to the above mentioned standard 2.5 mm^2 copper
conductor PVC insulated will be ok.
You have to check the voltage drop also: no more than 3%
rated and 10% at start. If DV=1.73*I*[R*cos(fi)+X*sin
(fi)].R,X =total resistance-at 70 dgr.C- and reactance
[ohm].
cos(fi)=0.85 [approx.] rated and 0.3 at start. Sin(fi)=
(1-cos(fi)^2)^0.5.
In this case if the cable length will be 80 m 4 mm^2 copper
conductor has to be employed.
| Is This Answer Correct ? | 6 Yes | 0 No |
Post New Answer View All Answers
A TRANSFORMER 440/400V,DELTA/STAR CONNECTED.THE NEUTRAL CONNECTED WITH GROUND CABLE THAT IS DIRECTLY CONNECTED TO THE PANEL,FROM PANEL IT IS CONNECTED EARTH PIT.IS IT RIGHT? IF IT IS RIGHT LEAKAGE CURRENT AFFECTED.SECONDATY IS PROTECTED WITH EARTH LEAKAGE RELAY.
what about electrical pannel.? What is meant by plc pannel.?
what will be d.g. capacity to cater together for 14hp A.C. load & 3kw lighting load
In control room of our one plant there is a continuously the incoming power goes to PC is vary,means in stabilizer it continuously indicate from high input to low and low input to high. what is the reason and its solution.
1600 KVA ka transformer hi aghar lt side par 800A aur voltage 420 ho to HT side ki cable ki rating keya ho gi?
is all the servo motors having brake?please specify which servo motors having brake for stop on position and which are not.
What is the formula formula for Busbar sizing and what are the things to be consider for Busbar Calculation?
Explain about 3 phase motor fault current calculation with examples?
how can motor both beasrings insulation resistance can be check?
how you taken aotitude test
WHY THE RATINGS OF THE TRANSFORMER IS 33KV WHY NOT OTHER???
how to conduct dc resistance test for rotor of an alternator and how to measure the rotor dc resistance value theoritically?
WHAT IS THE MEANING OG (li = 7 In)
63MVA,220KV/6.9KV Transformer LV side neutral is connected to Earth pit through NGR. Whether this earth pit required to connect with near by below grouding earth mat or it is to be kept separate?
In 11/0.414 KV Parralel supply network with Bus tie closed what will be the fault level is it doubled or halved??