why dc series moter is not started at no load?
Answer Posted / abhishekkumar
Motor armature current is decided by the load. On light load or no load, the armature current drawn by the motor is very small.
In case of a d.c. series motor,
Φ α Ia
and on no load as Ia is small hence flux produced is also very small.
According to speed equation,
N α 1/Φ as Eb is almost constant.
So on very light load or no load as flux is very small, the motor tries to run at dangerously high speed which may damage the motor mechanically. This can be seen from the speed-armature current and the speed-torque characteristics that on low armature current and low torque condition motor shows a tendency to rotate with dangerously high speed.
This is the reason why series motor should never be started on light loads or no load conditions. Foe this reason it is not selected for belt drives as breaking or slipping of belt causes to throw the entire load off on the motor and made to run motor with no load which is dangerous.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
List examples of voltage source?
1.what is difference between ATS & STS main use. 2.what is difference between ACB& VCB With symobles,and main partes, manimum range. 3.How many types of relays and main function.
how flow current in 220 kv line to line
Define filter?
Can you used moeller lzm1 mccb in a dc system with 125vdc and 20ka short circuit current , beside is it have 24 or 48 volt shunt ? Beside how long current can through from An MCB shunt contacts? (like Z7-AS 24 V)?
how can you size an automatic voltage regulator?
what is difference between isolation and ultra isolation transformer?, what is the method of testing ?
WHERE NEUTRAL WIRE IS CONNECTED AT DOMESTIC TO TRANSMISSION LINE(SINGLE PHASE TO THREE PHASE)
plese send me the oces/dgfs sylabus and previous year question pattern of electrical engg.?
Explain the operation of grid connected central solar inverter ?
how to estimate wiring ins roughing ins. and boxes
What is the relationship between voltage,current & frequency?
what is meant by IGBT how they differ from tyristor ?
WHTA IS LIMT OF LEAKGE CURRENT OF 11 KV 1 CORE 1000SQ.MM. XLPE CABLE.LOAD ON CABLE IS AROUND 600AMP .LENGTH 500 MTRS.
Please clarify, 1. Is it required to lay two runs of GI wire along with Armoured LT cable if it is laid between one big mains (63Amps TPN SDF) to small main (32A TPN SDF) with proper glanding termination? 2. If the armoured cable with proper glanding is laid from DB to CNC machine, is it required to run two runs of body earthing to the Machine from DB? 3.If the armoured cable with proper glanding is laid from Substation to Hangar, distance is approx. 100 mtrs, is it required to do earthing at shop area though the primary termination at substation is earthed through gland.