why dc series moter is not started at no load?
Answer Posted / abhishekkumar
Motor armature current is decided by the load. On light load or no load, the armature current drawn by the motor is very small.
In case of a d.c. series motor,
Φ α Ia
and on no load as Ia is small hence flux produced is also very small.
According to speed equation,
N α 1/Φ as Eb is almost constant.
So on very light load or no load as flux is very small, the motor tries to run at dangerously high speed which may damage the motor mechanically. This can be seen from the speed-armature current and the speed-torque characteristics that on low armature current and low torque condition motor shows a tendency to rotate with dangerously high speed.
This is the reason why series motor should never be started on light loads or no load conditions. Foe this reason it is not selected for belt drives as breaking or slipping of belt causes to throw the entire load off on the motor and made to run motor with no load which is dangerous.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
what is the k var ratting of 1250kva
What are marginally stable systems?
TRANSFORMERS WITH DC SUPPLY
What is the formuala to calculate the rating of motor protection circuit breaker
In Plumbing services What are accessories we consider for a bathroom?
What does the letter CTNM in negative phase sequence relay means?
Is it required to lay GI wires along with GI/MS conduits from one point to another point though separate earthing cable is conncted from DB to Socket?
What is the percentage loss for aluminium wire for HT line more than 11KVa
how is working bearing heater?
Can i use the B-curve MCB instead of C-curve MCB
why ahould you show client/engineer activities clearly on the project plan
Why you want to join non technical field when you are an engineer?
What is difference and reason b/w -48V BTS system and 24 V BTS system. Plzzzzzzzzz tel me.
we have 3 single phase transformers. how will we generate 6 supply from 3 phase supply input
how can decide the current rating of oltc