what is GRR(Grid Rotot resistance)?Why it is used beside of
LRS?
Answer Posted / rupesh usadadiya
GRS= Grid resistance STARTER
GRR= Grid resistance REGULATOR
While:LRS = Liquid Resistance STARTER
& LRR = Liquid Resistance REGULATOR
Both GRR & LRR or GRS & GRS are technically similar.
In both the equipment we are adding the resistance in the
rotor circuit.
BUT THE MAJOR DIFFERENCES ARE:
GRR a solid form of resistance, While LRR is Liquid form of
Resistance.
In GRR onece you define the resistance value, we can not
change the resistance value without changing the hardware.
While in LRR we can change the resistance value by changing
the Liquid concentration(PH).
In Regulators, the resistance is continue in circuit, hence
the temperature of resistance increase.
In solid resistance its possible to withstand the high
temperature without major changes in resitance value, while
in Liquid Resistance if temp. goes above 90 degree C, the
resistance value is change drastically.
Hence the Grid(Solid) resistance mainly used in speed
regulators.
If we want to use the Liquid Resistance as a controller,
then we need to add a heat exchange or cooling system to
maintain the Liquid temperature.
Any one can find out the more details on GRS/GRR and LRS/LRR
on www.resistancestarter.com or www.pew-india.in
| Is This Answer Correct ? | 43 Yes | 4 No |
Post New Answer View All Answers
The advantages of Magnetic flux leakage technique over Ultrasonic technique for non distructive testing of material.
Ac generato how produce power I need for camplet defination
what are the interview question asked in wind mill about electrical
What happens to voltage when current through the inductor is constant?
why does connected a indutor with mnsformeretering core of current transformer ?
What happens to a line-frequency of high-frequency transformer when it is first energized/ re-energize?
Why we are use dol starter up to 10 hp
What are the advantages of skewing of cage rotor conductors?
what is the solution for meger test failed the MV cable?
sir,in our plant we r using SATEC PM172E power reading meeters in HT panel side it is monitoring the MB data smart viewer(sever).but last one week we did not get readings inthe server only available in meeter.tell me how communicate meter and server. and also what steps we take for checking.
HOW TO SELECT THE COPPER CABLE SIZES OF MOTORS,TRANSFORMERS?
What are the two types of compensation?
what is the correct method for the outdoor termination of 19/33 KV HT cable step by step?
how to test the electrical panel.ht lt mcc pcc.
WHY BREAKER ARE USED IN SUBSTATIONS?