How to calculate & connection of 900KVA generator
2 sets & load(1500A)?
How to choose cable size and ACB size for this load &
generator?
please explain me detail.
Regards,
Mr.Han
Answer Posted / ganesh
All dg 9oo*1.39a =1251a (415v , pf .8,)
1251*1.5 time full load current 1876 A
you choose 2000A breaker
300*6 sq mm2
or 225*7 SQMM2
| Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Name of the relay of low lub oil presuure in DG sets
what are the different kind of cables used for transmissions?
In 11/0.414 KV Parralel supply network with Bus tie closed what will be the fault level is it doubled or halved??
Determine the BTU size of an aircon for 20 sq metre room
100 MVA 3-phase alternator with earthed neutral has a reactance of 5 ohms per phase. what will be the fault MVA of generator.
What is bode plot?
i need about 10 years of GATE solved papers in pdf format and even mock tests toooo
can i use ups power as a raw power for another ups
I am having a 42KW 3 phase electrical heating furnace, heating element is 80/20 nichrome material, my connections is made in such a way that 2 star connection compromising 2 coils per phase so totally 12 coils, shall if i use it unbalanced star condition (instead of 2 group of 3 phase or 1 group of 3 phase, connecting 4 phases of 5 phases) what will be the consequences and is it acceptable?
How i can calculate current of cable according to ares?
Define the term Capacitance and Inductance?
what is the relationship between phase & neutral
what is the difference between megger and earth resister ??
what do you mean by plant earthing system.
Dear all, how we select the cable size according to current with or without including different correction factor , is there any direct method for sizing of cable...